beautypg.com

Burnham Series 5B User Manual

Page 57

background image

57

(d) By referring to the Sequence of Operations

step-by-step operation of the system can

be controlled and the cause of pilot failure

can be readily found. After the cause of

the pilot failure has been corrected, resume

normal operation by following the Lighting

Instructions.

(3) SHUTDOWN INSTRUCTIONS

(a) Close manual shut-off valves and pilot

valves.

(b) Turn off main electric switch.

8

. EP CONTROL SYSTEM – 5015B thru 5026B

The 5015B thru 5026B boilers utilize two EP control

systems that are interconnected electrically thru all

operating and safety controls. Should any of the

aforementioned controls break the power supply circuit,

both EP control systems would be de-energized. The

succeeding paragraphs describe the function and

operation of each EP Control System. Should a pilot

failure on one EP Control System occur, the other EP

Control System would not be affected. Thus main

burners on the unaffected side would ignite on a “call

for heat” and would continue to operate until the

operating control was satisfied.

The EP Control System utilizes and RM7890A Relay

Module and a Q179C Rectification Pilot, which in

addition to a pilot burner and rectifying flame rod flame

detector to prove pilot, includes an ignition electrode

for spark ignition of the pilot. A Webster 612-6A7

Transformer supplies the high voltage spark potential.

Once pilot flame is proven, ignition stops but pilot

flame continues as long as there is a “call for heat”

(intermittent electrically ignited pilot).

The RM7890A Primary Control is a non-programming

amplifying relay which when used with the Q179C

Pilot provides solid state electronic Flame Safeguard

Protection that will not allow the main gas valve to

open on “call for heat” or that will shut down main

burners within 0.8 second if pilot flame is not “proved”.

Relay Module will lock out on safety shutdown within

15 seconds if there is a pilot flame failure on start or, if

during the “run” cycle, pilot flame is not re-established.

Since #8 terminal in the Relay Module is de-energized

at end of safety switch timing, a solenoid valve in the

pilot line will close and thus 100% shut-off is achieved.

a. OPERATING INSTRUCTIONS

(1) Make sure all Manual Main Shut-off Valves and

all Pilot Valves have been off for at least five

minutes.

(2) Set Operating and Limit Controls to desired

setting.

(3) Turn all Manual Main Shut-off Valves and Pilot

Valves to Open Position.

(4) Turn on Main Electric Switch and Service

Switch. Pilots will automatically light main

burners.

Proceed to Paragraph 15

- Minimum Input

Adjustments (for diaphragm “Lo-Hi-Lo” or

motorized type gas valves)

SEQUENCE OF OPERATION EP – See Fig. 49
a. NORMAL OPERATION – 5015B thru 5026B

1. When the operating control calls for heat,

terminal #6 of each RM7890A is energized.

2. A component check circuit in each RM7890A is

activated which checks the electronic network of

the relay.

3. Terminals #8 and #10 of each RM7890A relay

are energized. Terminal #8 opens the pilot line

solenoid valve supplying gas to the Q179C pilot.

Terminal #10 energizes ignition transformer

creating electric spark ignition at the Q179C

pilot.

4. Flame rod circuit between each Q179C pilot and

terminal “11” on its respective RM7890A proves

presence of flame electronically at its Q179C

pilot.

5. Terminal #10 of each RM7890A and the ignition

transformer connected to it is de-energized.

6. Terminal #9 on each RM7890A is energized

supplying power to its respective main gas

valves.

7. Main gas valves open and main burners are

ignited by the pilot flames.

8. When the operating control is satisfied, terminals

6 and all other terminals on both RM7890A

relays are de-energized. The main gas valves

and pilot valve for each gas train are closed

and main burners and pilot burner flames are

extinguished.

b. SAFETY SHUTDOWN

(1) SAFETY SWITCH CIRCUIT

If limit control, low water cut-off or any other

electrical safety switch opens, power to terminal

6 and all other terminals on both RM7890A

relays are interrupted de-energizing the main

gas valves and pilot valves and the main gas

burners and pilot burners are immediately

extinguished. Normal operation can be resumed

when the cause of the safety switch malfunction

is corrected. Make sure all manual resets are

activated where applicable.

(2) PILOT FAILURE

(a) Pilot failure can occur during the start and

operating cycle of the boiler. Any pilot

failure on either of the Q179C Electronic

SecTiON iV - OPeRATiON (continued)