beautypg.com

Burnham Series 5B User Manual

Page 63

background image

63

FIG. 53

LOW FIRE ADJUSTMENT - V4062 ACTUATOR

(3) Remove the lead to V9055A terminal R.

Jumper terminal R to W. This will prevent the

actuator from going to the high fire position.

(4) Energize the system and light the main burner.
(5) Use a Phillips screwdriver, or standard type with

a blade no more than 3/16 inch wide, to turn

the low fire adjusting screw for the desired low

fire position. DO NOT PUSH INWARD ON

SCREW.

(6) Shut down the burner, and then restart. Repeat

several times to be sure the low fire setting is

that desired and suitable for correct burner light

off.

(7) Turn off power supply. Remove R-W jumper,

and reconnect the lead to terminal R on the

V9055A.

(8) Replace the wiring compartment cover.

FIG. 54

LOW FIRE ADJUSTMENT - V9055A ACTUATOR

16.

MAIN BURNER FLAMES should have a clearly

defined inner cone, see Fig. 59 with no yellow tipping.

Orange-yellow streak caused by dust should not be

confused with true yellow tipping.

17

. CHECK PILOT FLAME. Flame should be a blue

medium hard flame enveloping approximately 3/8” of

the end of the thermocouple, flame sensor, or sensing

probe, see Fig. 60 thru 63.

SecTiON iV - OPeRATiON (continued)