beautypg.com

Burnham ALP080 User Manual

Vi. water piping and trim, Warning, General information

background image

VI. Water Piping and Trim

Supplemental Instructions

Recommended Circulator Models

Alpine™ Condensing High Efficiency

Direct Vent Gas-Fired Hot Water Boiler

The information below supplements information contained in Installation, Operating and Service Instructions for Alpine™

Condensing High Efficiency Direct Vent Gas-Fired Hot Water Boiler, Part No. 101602-01. Follow Supplemental Instructions and

details outlined below until directed otherwise.

WARNING

Prior to attempting any service on this boiler, read, understand and follow all instructions as outlined in

this supplement and also the Installation, Operating and Service Instructions which was provided with the

boiler.

GeneRal InFoRMatIon

These instructions contain supplemental revised information related to recommended circulator models for

Alpine™ boilers. Refer to Installation, Operating and Service Instructions manual for all other installation

instructions. Where applicable, substitute these instructions, paragraph for paragraph, for the information

outlined in the Installation, Operating and Service Instructions manual provided with the boiler.

0297-0R-7/08

Boiler

Model

Boiler Supply

Connection,

Inch, FPT

Boiler Return

Connection,

Inch, FPT

Near-Boiler

Piping

Supply Pipe

Size, Inch

Near-Boiler

Piping

Return Pipe

Size, Inch

Flow, GPM

@ 25°F Temp.

Differential

Combined

Boiler & Piping

Loop Head

Loss, Ft.

* Recommended

Circulator

Make & Model

ALP080

1

1

1

1

5.8

10.3

Taco 0010

Grundfos UPS

15-58 FRC

ALP105

1

1

1

1

7.7

15.1

Taco 0014

Grundfos UPS

26-99 FC (second speed)

ALP150

1

1

1

1

11.0

13.1

Taco 0014

Grundfos UP

26-99 FC (first speed)

ALP210

1

1

15.5

12.7

Taco 0014

Grundfos UP

26-99 FC (first speed)

ALP285

21.5

13.0

Taco 0013

Grundfos UP

26-99 FC (third speed)

ALP399

2

2

30.2

12.0

Taco 1400-20

Grundfos UPS

32-80/2 F (second speed)

Notes:

* Circulator Models shown are not equipped with internal flow check valve (IFC).

When selecting Circulators with IFC contact Circulator Manufacturer for sizing information.

Near-Boiler Piping Size shown is based on 2 to 5.5 Ft/Sec. velocity range to avoid potential noise and pipe erosion.

Table 9 : Recommended Circulator Models for Alpine (ALP) Boilers Based on 25°F Temperature Differential

and Up to 75 ft. Equivalent Length Near-Boiler Piping