beautypg.com

Burnham Series 5B User Manual

Page 39

background image

39

Venting

1.

INSTALL VENT CONNECTOR from canopy Draft

Hood or damper to chimney maintaining 6” clearances

from combustible materials.

2.

INSTALL VENT SYSTEM – Typical vent systems are

shown in Fig. 40 and 41. Some of the factors affecting

vent sizing and construction accompany these figures.

Vent installation shall be in accordance with local

building codes; or the local authority having

jurisdiction; or the National Fuel Gas Code, ANSI

Z223.1/NFPA 54; or the Standard for Chimneys,

Fireplaces, Vents and Solid Fuel Burning Appliances,

ANSI/NFPA 211. Both of the aforementioned

standards, ANSI Z223.1 and ANSI/NFPA 211,

specify Type B and Type L double wall metal vents

and fire clay tile lined masonry chimneys as suitable

chimney constructions for Category I, draft hood

equipped appliances, such as this Series 5B boiler.

Both standards prohibit the use of unlined masonry

construction as a chimney, with the exception in

ANSI Z223.1/NFPA 54 that “Where permitted by

the authority having jurisdiction, existing chimneys

shall be permitted to have their use continued when

an appliance is replaced by an appliance of similar

type, input rating and efficiency.” ANSI/NFPA 211

prohibits the use of single wall metal vent as a chimney,

while ANSI Z223.1 allows it under very restrictive

conditions.

In Canada, refer to CAN/CSA-B149.1 or .2-M86 and

local codes for venting.
SOME ITEMS RELATIVE TO CONSTRUCTION

AND SIZING OF VENT SYSTEM

(1) Total Vent Height.
(2) Vent Connector – make Initial Rise as high as

possible.

(3) Length of Lateral – hold to a minimum.
(4) Number of Elbows – hold to a minimum.
(5) UL Listed Vent Cap – assures full vent capacity

and freedom from adverse wind effects.

(6) Locate Boiler as close to Chimney as possible

consistent with necessary clearances, see page 7,

lower table.

(7) Run Breaching Horizontal and slope upward to

Chimney maximum of ¼” per ft.

(8) Use thimble where Breaching enters masonry

chimney – keep breaching flush with inside of flue

liner – do not connect into same leg of chimney

serving an open fireplace.

(9) Install vent above bottom of Chimney to prevent

blockage – inspect chimney for obstructions

or restrictions and remove – clean chimney if

necessary.

FIG. 40

SINGLE VENT SYSTEM

FIG. 41

MANIFOLD VENT SYSTEM

(10) Provide cleanout in chimney.
(11) Slip joint or draw band – facilitates installation and

future servicing when necessary.

(12) Venting of other appliances into same chimney

or into a common vent will affect sizing of the

chimney or common vent.

(13) Correction for altitude – design vent system for sea

level input.

(14) Provide adequate ventilation of Boiler Room, see

page 7 – this cannot be overemphasized.

(15) Never pass any portion of a vent system thru a

circulating air duct or plenum.

(16) Support of lateral runs so that vent pipe does not

sag.

(17) Support of common vent where it passes thru a

ceiling or roof.

SecTiON iii – iNSTALLATiON iNSTRUcTiONS (continued)