beautypg.com

Burnham Series 5B User Manual

Page 54

background image

54

and the relay will lock out on safety within

15 seconds.

Assuming the pilot on the opposite side is

burning, the gas valves on that side will

open and main flame will be ignited on that

side only.

7

. EP CONTROL SYSTEM – 5006B thru 5014B

The EP Control System utilizes an RM7890A Relay

Module and a Q179C Rectification Pilot, which in

addition to a pilot burner and rectifying flame rod flame

detector to prove pilot, includes an ignition electrode

for spark ignition of the pilot. A Webster 612-6A7

Transformer supplies the high voltage spark potential.

Once pilot flame continues as long as there is a “call for

heat” (intermittent electrically ignited pilot).

The RM7890A Relay Module Primary Control is a

non-programming amplifying relay which when used

with the Q179C Pilot provides solid state electronic

Flame Safeguard Protection that will not allow the main

gas valves to open on “call for heat” for that will shut

down main burners within 0.8 second if pilot flame is

not “proved”. Relay Module will lockout on safety

shutdown within 15 seconds if there is a pilot flame

failure on start or, if during the “run” cycle, pilot flame

is not re-established. Since #8 terminal in the Relay

Module is de-energized at end of safety switch timing, a

solenoid valve in the pilot line will close and thus 100%

shut-off is achieved.
a. OPERATING INSTRUCTIONS

(1) Make sure Manual Main Shut-off Valve and

all Pilot Valves have been off for at least five

minutes.

(2) Set Operating and Limit Controls to desired

settings.

(3) Turn Manual Main Shut-off Valve and Pilot

Valve to Open Position.

(4) Turn on Main Electric Switch and Service

Switch – Pilot will automatically light main

burners.

SEQUENCE OF OPERATION EP - See Fig. 48
b. NORMAL OPERATION - 5006B thru 5014B

(1) When the operating control calls for heat,

terminal #6 of RM7890A Relay is energized.

(2) A component check circuit in the RM7890A

Relay is activated which, checks the electronic

network in the relay.

(3) Terminals #8 and #10 of the relay are energized.

Terminal #8 opens pilot line solenoid valve

supplying gas to pilot. Terminal #10 energizes

ignition transformer creating electric spark

ignition at pilot.

(4) Flame rod circuit between Q179C pilot and

RM7890A proves presence of pilot flame

electronically.

(5) Terminal #10 to ignition transformer is de-

energized.

(6) Terminal #9 is energized and supplies power to

the main gas valves.

(7) Main gas valves open and main burners are

lighted by pilot.

(8) When operating control is satisfied, terminals

#6 and #9 are de-energized. Main Gas Valves

and pilot line solenoid valve are all de-energized

and main burner and pilot burner flames are

extinguished.

c. SAFETY SHUTDOWN

(1) SAFETY SWITCH CIRCUIT

If limit control, low water cut-off or any other

electrical safety switch opens, power to terminal

#6 in relay is interrupted thus de-energized

terminal #9 and #8 in relay which de-energizes

main gas valves and pilot valves. Main gas

burners and pilot burners are immediately

extinguished. Normal operation can be resumed

when the cause of safety switch malfunction

is corrected. Make sure all manual resets are

activated where involved.

(2) PILOT FAILURE

(a) Pilot failure can occur during the start of

operating cycle of the boiler. Any pilot

failure, on the Q179C electronic pilot, after

ignition of pilot flame will close the main

gas valves in 0.8 second.

(b) For 15 seconds after failure of the Q179C

pilot, the relay through terminals #8 and #10

will try to establish pilot flame. If not pilot

flame can be sensed by the flame rod circuit,

terminal #8 and #10 are de-energized, and

the relay will lock out on safety.

(c) Pilot failure is caused by the following:

(1) Complete loss of gas supply.
(2) Poor ignition spark caused by low

voltage, poor ground connection, faulty

wiring, and possibly a defective ignition

transformer.

(3) Low gas pressure will prevent flame rod

circuit from sensing pilot flame properly.

(4) Unusually strong secondary air drafts

can blow the pilot flame away from the

flame rod momentarily causing nuisance

shutdown.

(5) A pilot line solenoid valve will not open

because of faulty wiring, low voltage, or

possibly the valve is defective.

(6) A defective RM7890A may be the cause

but items (1) thru (5) should be followed

first. Refer also to RM7890A relay

literature furnished with the control.

SecTiON iV - OPeRATiON (continued)