beautypg.com

Caution, Warning – Burnham Series 5B User Manual

Page 12

background image

12

FIG. 8

INSTALLATION OF BUILT-IN HEATER

FIG. 9

TESTING BOILER ASSEMBLY FOR LEAKS

Open Steam or Water Trim Carton

8.

USE THE PLUGS IN THIS CARTON to plug tappings

in End Sections that will not be utilized on final

installation, see Fig. 7.
Open Tankless Heater Carton(s) If Supplied.
Open Heater Opening Cover Plate Carton(s)
.

9.

INSTALL BUILT-IN WATER HEATER(S) OR

HEATER OPENING COVER PLATE(S), See Fig.

8. Heater may be installed in either End Section or,

in some cases, in both End Sections. Heater Opening

Cover Plates are used to cover any unused heater

openings.
a. Place rubber gasket against surface of plate and

align holes.

b. Place washer on each of 3/8” Cap Screws furnished

and insert cap screws through plate and gasket.

Start all screws in taps before final tightening.

10.

HYDROSTATIC TEST, see Fig. 9: After the boiler

sections have been assembled, it is essential that the

boiler be hydrostatically tested before the canopy, flue

cover plates, jacket, or piping is installed.
a. Plug all boiler tappings and fill boiler completely

with cold water.

cAUTiON

DO NOT install gauge until after hydrostatic

testing the boiler. Gauge failure may result.

b. All completed boilers must satisfactorily pass the

prescribed hydrostatic test.
(1) STEAM BOILERS: The assembled boiler must

be subjected to a hydrostatic test of 45 psig to 55

psig.

(2) HOT WATER BOILERS: The assembled boiler

must be subjected to a hydrostatic test of 75 psig

to 85 psig.

WARNiNG

Failure to properly hydrotest all boilers at the

correct pressure may result in section assembly

failure in operation.

11.

EXAMINE BOILER CAREFULLY, INSIDE AND

OUTSIDE, to insure against leaks from cocked nipples

or through concealed breakage caused in shipping and

handling. This precaution is for your protection and

will simplify handling of necessary replacements and

adjustment claims. After making certain that there are

no leaks, drain boiler and remove plugs for boiler trim

and other connections.

Open Boiler Sealing Carton.

12.

SEAL BETWEEN BOILER SECTIONS AND BASE,

see Fig. 10.
a. Push ¾” braided ceramic fibre Rope (furnished) into

gap between bottom of End Section and Low Base

End Panel until rope touches Front and Rear Base

Frames. Place the 1-1/2” x 2” x 5/8” steel spacers

between low base panel and section and in front of

rope – align holes. Secure section to low base end

panel with 3/8”-16 x 2” Cap Screws, washers and

nuts.

b. Secure opposite end section to high base end panel

with 3/8”-16 x 2” Cap Screws, washers and nuts.

c. Apply Furnace Cement to gaps between section

assembly and base to make gas tight seal.

d. Check all joints between Boiler sections and use

remaining Furnace Cement or Sealer Compound to

make joints gas tight.

SecTiON iii – iNSTALLATiON iNSTRUcTiONS (continued)