58

Pilots, after ignition of pilot flame will close

the pilot valve and the main gas valves

controlled by that particular RM7890A relay

in 0.8 second. The burners controlled by the

other RM7890A will continue to burn.

(b) For 15 seconds after failure of a Q179C

pilot, the relay through terminals #8 and #10

will attempt to re-establish pilot flame. If no

pilot flame can be sensed by the flame rod

circuit in 15 seconds, terminals #8 and #10

are de-energized, and the relay will lock out

on safety.

(c) Pilot failure is caused by the following:

(1) Complete loss of gas supply.
(2) Poor ignition spark caused by low

voltage, poor ground connection, faulty

wiring, and possibly a defective ignition

transformer.

(3) Low gas pressure will prevent flame rod

circuit from sensing pilot flame properly.

(4) Unusually strong secondary air drafts

can blow the pilot flame away from the

flame rod momentarily causing nuisance

shutdown.

(5) A pilot line solenoid valve will not open

because of faulty wiring, low voltage, or

possibly the valve is defective.

(6) A defective RM7890A may be the cause

but items (1) thru (5) should be followed

first. Refer also to RM7890A relay

literature furnished with the control.

(d) By referring to the Sequence of Operations

step by step operation of the system can

be controlled and the cause of pilot failure

can be readily found. After the cause of

pilot failure has been corrected, resume

normal operation by following the Lighting

Instructions.

(3) SHUTDOWN INSTRUCTIONS

(a) Close manual shut-off valves and pilot

valves.

(b) Turn off main electric switch.

13.

THERMOCOUPLE CONTROL SYSTEM (Canada

Only)

The 5006B thru 5013B boilers are equipped with

a Thermocouple Control System that utilizes a

constant-burning Q327A pilot, a Q309 thermocouple,

and a L62GB-3C Pilot Safety Switch. The Q309

thermocouple proves pilot flame and, in the absence

of such, will cool and, within 45 to 90 seconds, will

cause the L62GB-3C Pilot Safety Switch to which it is

connected, to break the electrical circuit to the main gas

valves as well as shut off the flow of gas to the pilot.

Thus, 100% shut-off is achieved.

The 5015B thru 5024B boilers utilize two

Thermocouple Control Systems that are interconnected

electrically thru all operating and safety controls.

Should any of the aforementioned controls break the

power supply circuit, both Thermocouple Control

Systems would be de-energized. The proceeding

paragraph describes the function and operation of each

Thermocouple Control System. Should a pilot failure

on one Thermocouple Control System occur, the other

Thermocouple Control System would not be affected.

Thus main burners on the unaffected side would ignite

on a “call for heat” and would continue to operate until

the operating control was satisfied.
a. LIGHTING INSTRUCTIONS

(1) Make sure that all main manual and pilot valves

have been off for at least five (5) minutes.

(2) Set operating and limit controls to desired

setting.

(3) Open pilot valve.
(4) Depress button on pilot safety switch to which

it is connected and hold lighted match on pilot.

Hold button in for at least one minute, or until

the pilot burner remains lit after the button is

released. Repeat for second pilot when boiler is

so equipped.

(5) Open manual main shut-off valve(s).
(6) Turn on main electric switch.

NORMAL OPERATION SEQUENCE

5006B thru 5013B, see Fig. 50

5015B thru 5024B, see Fig. 51

SecTiON iV - OPeRATiON (continued)