RATE SCALING EXAMPLE: (Cont’d)

EXAMPLE #2: (Cont’d)

We now have all the information necessary to scale the rate. The Total Scaling,

“K

T

”, is calculated using Formula #1 as shown below.

K

T

= Display Units

¸

Number of Pulses = 810

¸

5600 = 0.144643

It is noticed that there are more significant digits in the Total Scaling, “K

T

”,

than there are available for the Scale Factor, “SF”. To acquire the maximum
amount of significant digits for the Scale Factor, Formula #2 is used and a Scale
Multiplier value of 0.1 is selected.

SF = K

T

¸

SCM = 0.144643

¸

0.1 = 1.4464

The Scale Factor, “SF”, equals 1.4464 (1.44643 rounded to 4 decimal places).

This provides the maximum amount of conversion accuracy possible.

The final step is to select a Rate Conversion Factor. The Rate Conversion

Factor is chosen to be Rate Per Minute as was required.