Red Lion LEGEND User Manual
Page 46
SENDING COMMANDS AND DATA (Cont’d)
VALUE IDENTIFIERS
MNEMONIC
A (41H) PRESET 1
P1
B (42H) PRESET 2
P2
C (43H) PROCESS SCALE FACTOR
SFP
S
D (44H) RATE SCALE FACTOR
SFR
S
E (45H) PROCESS
PRO
S
F (46H) BATCH
BAT
S
G (47H) TOTAL
T
S
H (48H) RATE
RAT
S
I (49H) PEAK
PEA
S
J (4AH) VALLEY
VAL
S
K (4BH) PRESET 3
P3
L (4CH) PRESET 4
P4
O (4FH) COUNTER LOAD
CLD
Q (51H) TOTAL SCALE FACTOR
SFT
S
Note: Command identifiers other than those listed should NOT be transmitted.
Otherwise, undefined or unpredictable operation could result.
S From Factory Settings, the mnemonic transmitted is based on full mnemonic
programmed in Display Module. The print mnemonic is the first three
characters of the full mnemonic. The printed mnemonics for the Scale Factors
is SF followed by the first character of the full mnemonic for the value
associated with the Scale Factor.
The command string is constructed by using a command, a value identifier, and a
data value if required. The Data value need not contain the decimal point since it is
fixed within the Legend Plus unit, when programmed at the front panel. The Legend
Plus will accept the decimal point, however, it does not interpret them in any way.
Leading zeros can be eliminated, but all trailing zeros must be present.
Example: If a Scale Factor of 1.0000 is to be sent, the data value can be
transmitted as 1.0000 or 10000. If a “1” is transmitted, the Scale Factor will be
changed to 0.0001.
The Address command is used to allow a command to be directed to a specific
unit on the Serial Communications Line. When the unit address is zero,
transmission of the Address command is not required. This is done for
applications that do not require more than one Legend Plus. For applications that
require several units, each Legend Plus on the line must be given a non-zero
address. If they are given the same address, a command such as the Transmit
Value Command, will cause all the units to respond simultaneously, resulting in a
communication collision. All Legend Plus units in a multiple unit application
should be given an address other than zero. If a unit has an address of zero, it will
attempt to process any transmissions from the other Legend Plus’s as commands.
These transmissions fill up the receive buffer of the unit with an address of zero,
which may produce unpredictable results.
The command string is constructed in a specific logical sequence. The Legend
Plus does not accept command strings that do not follow this sequence. Only one
operation can be performed per command string. Below is the procedure to be
used when constructing a command string.
1. The first two or three characters of the command string must consist of the Address
Command (N) and the address number of the unit (1 to 99). If the Legend Plus
address is zero, the address command and number need NOT be sent.
2. The next character in the command string is the actual command that the
Legend Plus is to perform (M, MC, P, R, T, or V).
3. A Value or command Identifier is next if it pertains to the command. The
command P (print) does not require a Value Identifier.
4. The numerical data will be next in the command string if the “Change Value”
command is used.
-44-