beautypg.com

Change display (chg dsp) 24, Request message (req msg#) 24, Clear message (clr msg) 24 – Red Lion LEGEND User Manual

Page 26: Skip preset (skip prs) 24, Counter load (cnt ld) 24, Print request (print rq) 24, Program disable (pgm.dis.) 24, Inhibit count 24

background image

PROGRAM USER MODULE (Cont’d)

CHANGE DISPLAY (CHG DSP)

In the indication display loop, when a User Input is activated, the indication

display toggles to the next indication display. The change of display is a
momentary action.

Activation of a User Input programmed for Change Display will suspend any

displayed message for 2.5 seconds.

REQUEST MESSAGE (REQ MSG#)

The selected message is requested when the User Input is activated. This may be

a maintained or momentary request, as selected in the Program Message Module.

CLEAR MESSAGE (CLR MSG)

When the User Input is activated, the displayed message is cancelled. This is a

maintained action. While this input is held active, it prevents messages from
being requested. Only one User Input should be programmed for the Clear
Message function.

SKIP PRESET (SKIP PRS)

Up to 4 Presets can be set to be skipped using one User Input. When the User

Input is activated, the output does not activate/deactivate when the count/rate
output conditions are met. This includes an Automatic Reset at Preset. The
counter continues to count through the preset.
Note: An individual preset may be programmed to be skipped on only one User

Input. Other User Inputs may be programmed for skipping presets only if the
presets selected are not programmed to be skipped elsewhere.

COUNTER LOAD (CNT LD)

The process count value is set to the counter load value, regardless of the

process reset action programmed in the Program Counter Module. If the batch
reset mode is programmed for counter load, the batch value is set to the counter
load value, and the process count is ignored.
Note: The counter load reset action should be programmed for only one count

display, either the process count or the batch count. The counter load is a
maintained action.

PRINT REQUEST (PRINT RQ)

When a User Input is activated, the unit transmits all the information selected in

the Print Options Module via the serial port. The print request is a maintained action.

PROGRAM DISABLE (PGM.DIS.)

This option used with the Program Disable DIP switch can limit operator

access to programmable parameters (Refer to Operator Accessible Functions
With Program Disable section). Only one external User Input can be used for this
option. The program disable is maintained.

INHIBIT COUNT

When active, the Input Count function prevents pulses from being counted

on Inputs A & B. The rate input is not affected by the Inhibit function, and
continues to indicate the rate of the signal at Input A. This function is only
available on User Input 4.

-24-