DECIMAL POINT (CNT. DP, RATE DP, TOT DP)

There are six Decimal Point locations available for the Rate, Total and Process

displays. The decimal point position is programmed individually for each
display. The decimal point location programmed for the Rate display is the same
for the Peak and Valley displays.

CHANGE COUNT VALUE WITH SCALE FACTOR (CHG CNT W/SF)

Any changes to the count or total scale factors adjust the currently displayed count

and total values to reflect the new scale factor. If this option is set to no, the internal
count value is modified so that the count and total display values are not affected.

Example; a count scale factor of 1.000 with a count value of 36 and a total

value of 4 is changed to a count scale factor of 0.500. If the option is set to yes, the
new count value would be 18 and the new total value, 2. If the option was selected
as no, the count and total display values would remain at 36 and 4.