10. CONTROL INPUTS:

Programmable User Inputs (4):

USR INP 1 to 3: Internal 10 K

W pull-up to +5 VDC, V

IL

= 1.5 V

MAX

; V

IH

=

3.5 V

MIN

, response time = 30 msec typical, 100 msec max. (count rate

dependent).

USR INP 4/INH: Internal 10 K

W pull-up to +5 VDC, V

IL

= 1.5 V

MAX;

V

IH

= 3.0 V

MIN

, response time = 30 msec typical, 100 msec max.

(count rate dependent).
INHIBIT Response time = 50

msec max.

User Inputs Programmed for Binary Message Request: Debounce =

100 msec. (Binary Message Request Inputs must be stable for 100
msec. before a message is requested).

11. SERIAL COMMUNICATIONS:

Type: Jumper selectable RS-485 or RS-232.

Can connect up to 32 units when using RS485 interface.

Baud Rate: Programmable from 1200 to 9600.
Maximum Addresses: Programmable from 00 to 99.

(Actual number on a line is limited by hardware specifications)

Transmit Delay: Programmable for 0.002 or 0.100 second.
Data Format: 10 Bit Frame; 1 start bit, 7 or 8 data bits, 1 or no parity bit, and 1
stop bit. Parity is programmable for either ODD (7 data bits), EVEN (7 data
bits), or NO Parity (8 data bits).

12. OUTPUT(S):

Solid-State: Current sinking NPN open collector transistor. V

CE

= 1.1 V

SAT

@

100 mA max. V

OH

= 30 VDC max. (Internal Zener Diode Protection).

Relay(s): Mounted on field-replaceable P.C. board. Form C contacts rated

at 5 amps @ 120 VAC/240 VAC or 28 VDC (resistive load), 1/8 H.P. @
120 VAC (inductive load). The operate time is 5 msec nominal and the
release time is 3 msec nominal.

Programmable Timed Output(s): Programmable time ranges from 0.01

to 99.99 seconds, ±0.05% - 11 msec. max.

Count Boundary Output Response Time: 10 msec nominal.
Output Time Required to Request Message: 50 msec.

13. ENVIRONMENTAL CONDITIONS:

Operating Temperature: 0 to 50°C
Storage Temperature: -40 to 80°C
Operating and Storage Humidity: 85% max. max. relative humidity

(non-condensing) from 0°C to 50°C.

Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z

direction for 1.5 hours, 2 g.

Shock According to IEC 68-2-27: Operational 20 g (10 g relay), 11 msec

in 3 directions.

Altitude: Up to 2000 meters

14. CERTIFICATIONS AND COMPLIANCES

SAFETY

IEC 6 1 0 1 0 -1 , EN 6 1 0 1 0 -1 : S a f e t y req u i remen t s f o r e l e c t ric a l

equipment for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529
Type 4X Indoor Enclosure rating (Face only), UL50

ELECTROMAGNETIC COMPATIBILITY

Immunity to EN 50082-2

Electrostatic discharge

EN 61000-4-2 Level 2; 4 Kv contact

Level 3; 8 Kv air

Electromagnetic RF fields

EN 61000-4-3 Level 3; 10 V/m

80 MHz - 1 GHz

Fast transients (burst)

EN 61000-4-4 Level 4; 2 Kv I/O

1

Level 3; 2 Kv power

RF conducted interference

EN 61000-4-6 Level 3; 10 V/rms

1

150 KHz - 80 MHz

Power

frequency magnetic fields EN 61000-4-8 Level 4; 30 A/m

Emissions to EN 50081-2

RF interference

EN 55011

Enclosure class A
Power mains class A

Note:
1. When the unit is DC powered from terminal TBA pin 5 (common) and

terminal TBA pin 3 (DC OUT/IN) a power line filter was installed, RLC
#LFIL0000 or equivalent, so as not to impair the function of the unit.

Refer to EMC Compliance Installation for additional information

15. CONSTRUCTION: High impact plastic case with clear viewing window.

The unit is rated for NEMA 4X/IP65 indoor use. Installation Category II,
Pollution Degree 2 Panel gasket and mounting clips included.

16. WEIGHT: 1.5 lbs. (0.68 Kg)