SPECIFICATIONS & DIMENSIONS

1. DISPLAY: 2x8, 0.3" (7 mm) high characters, negative image transmissive LCD,

with Single (green or red) or Dual Color (green and red) LED backlighting.

2. POWER:

AC Operation: 115/230 VAC

±10%, 50/60 Hz, 10 VA, switch selectable.

DC Operation: +12 VDC

±20% @ 250 mA. max.

3. MEMORY: Non-volatile memory retains all programming information.

Count and Preset values are written to non-volatile memory when power is
interrupted. All other programming parameters are written to memory when
programming mode is exited. If power is removed while in the programming
menus, the parameters are restored to previously saved settings.
Data Retention: 10 years min.
Message/Mnemonics Memory: 792 bytes available (with factory settings
loaded).

4. SENSOR POWER: +12 VDC

±25% @ 100 mA.

5. INPUTS A and B: DIP Switch selectable to accept count pulses from a variety

of sources including switch contacts, outputs from CMOS or TTL circuits, and
all standard RLC sensors.
LOGIC: Input trigger levels V

IL

= 1.5 V

MAX

; V

IH

= 3.75 V

MIN

.

Current sinking: Internal 7.8 K

W pulled up to +12 VDC , I

MAX

= 1.9 mA.

Current sourcing: Internal 3.9 K

W pull-down, 7.3 mA @ 28 VDC

MAX.

Debounce: Damping capacitor provided for switch contact bounce. Limits

count speed to 50 Hz and input pulse widths to 10 msec minimum.

MAGNETIC PICKUP:

Sensitivity: 200 mV peak.

Hysteresis: 100 mV.
Input impedance: 3.9 K

W @ 60 Hz.

Maximum input voltage:

±50 Vp

Note: For magnetic pickup input, the sink/source DIP switch must be in the

SRC position.

6. RATE ACCURACY: +0.01%.
7. RATE MINIMUM INPUT FREQUENCY: 0.01 Hz.
8. MAXIMUM COUNT RATE IN KHz:

MODEL

CNT + DIR

QUAD

ADD/ADD

ADD/SUB

X1

X2

X1

X2

X4

X1*

X1*

LGPB

15

7

7

5.5

3

14

7

NOTES:

1. Maximum count rates given are for Process counter set for Auto reset with the auto cycle preset

set to an equivalent of 100 count pulses or greater. With auto cycle presets less than 100

counts the maximum count ry be lower. The actual preset value for 100 count pulses, with

Count SF = 0.5000 and Count Scale Multiplier = X1, would be 50.

2. Maximum count rate given for X2 & X4 count modes are given for 50% duty cycle signals and

Quad signals with 90° phase shift.
S - Inputs A & B count rates summed.

9. MAXIMUM COUNT CAPACITY:

Process or Count: 9 digits internal (non-scaled),

6 digits displayable (scaled).

Batch Count: 6 digits.
Total Count: 11 digits internal (non-scaled),

8 digits displayable (scaled).

-57-

DIMENSIONS In inches (mm)

Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 3.0" (76.2)H x 4.0" (101.6)W.

PANEL CUT-OUT