If you select enclosures, licensed servers, and unlicensed servers to license the unlicensed servers and generate
power management reports, the selected enclosures are removed from the selected targets when you click
Previous on the License unlicensed servers page.
Solution 1: Take the following steps to resolve the problem:
1.
License the unlicensed servers.
2.
Select the enclosures along with the licensed servers to generate the power management reports.
Solution 2: On the License unlicensed servers page, you must not click Previous. After the unlicensed
servers are licensed and when you click Next, the enclosures are listed on the next page.
Unable to view/receive iLO 2 power threshold alerts.
Solution: Perform the following to resolve the problem:
•
Using iLO 2 Web Interface, you need to configure the CMS server to receive SNMP alerts from iLO 2.
•
From Systems Insight Manager, you need to configure cpqHo2PowerThresholdTrap defined in
cpqHost.mib on the SNMP Trap Settings (Options
→Events→SNMP Trap Settings) page.
•
On power threshold breach, iLO 2 sends SNMP alerts, which are logged against the system and can
be viewed from Events tab of the System page.
Unable to communicate with Management Processor
because the Management Processor does not have a serial number and(or) network
address. Please re-identify the Management Processor and try again.
Solution: There might be a problem with duplicate iLOs associated with the system. Use the All Management
Processors
view and identify the iLOs associated with the server. There is one iLO with its name being the
IP address of the iLO and another iLO with the serial number of the iLO as its system name. Delete the iLO
with no IP address recorded.
Discovery of PDU/PDR does not create Power Delivery Devices.
Solution: If the Breaker Panel, Branch Circuit, Rack PDU, or Load Segments associated with the PDU/PDR
management module are not discovered properly, verify the PDR/PDU monitoring via SNMP configuration
settings. See
Configuration for PDR/PDU monitoring via SNMP
. After making the required changes, select
and identify the system using Systems Insight Manager's Identify Systems option. You will see the following
identifying systems output to enable discovery/monitoring of the PDU/PDR:
* Checking for SNMP protocol support on system.
Result: The system responded to an SNMP request;
it supports SNMP.
...
* Checking if this system is supported by
Insight Control power management.
* Insight Control power management is supported.
For the incorrect PDU/PDR settings, the message will be displayed as:
* Checking for SNMP protocol support on system.
Result: The system did not respond to SNMP.
Verify security settings and community strings
in Options->Security->Credentials->System Credentials.
...
* Checking if this system is supported by
Insight Control power management.
* Insight Control power management is not supported.
80