42 config

Command Example

Root>

config switch priority principal

config.switch.raTOV

Syntax

raTOV timeoutValue

Purpose

This command sets the R_A_TOV for the switch.

Description

The switch must be set offline before this command is entered.

Special care should be used when scripting this command due to its relationship with
E_D_TOV.

Parameters

This command has one parameter.

Command Example

Root>

config switch raTOV 20

timeoutValue

Specifies the new R_A_TOV value. The units for this value are tenths of a
second. This parameter must be an integer in the range 10–1200 (1 second
to 120 seconds), and it must be larger than the E_D_TOV.