beautypg.com

Ups upgrade, Ups upgrade 195, Adding a ups 195 – HP StorageWorks 8000 NAS User Manual

Page 197

background image

NAS 8000 System and Hardware Upgrades 195

NA
S 80
00

S

ys

tem

a

nd

Har
dwar
e Upg
ra

de

s

UPS Upgrade

Adding a UPS

The following UPS systems can be added to the HP NAS 8000 solution after

the time of purchase. The specific model of UPS recommended is customized

each region:

American Power Conversion (APC) Symmetra RM (8U)

American Power Conversion (APC) Symmetra RM (15U)

American Power Conversion (APC) Symmetra

To install the UPS on the HP NAS 8000 solution, follow these steps:

1

Follow the instructions that came with the UPS for power requirements.

2

Power down all of the solution components in the following sequence

before installing the UPS:

NAS server(s)

Quorum server (for high-availability configurations)

Array

FC switch (for high-availability configurations)

Library

3

Install the UPS in the bottom of the rack to avoid having a top-heavy rack

and to eliminate the risk of tip over.

4

Connect the communications port on the UPS to the server's COM1 serial

port.

5

Plug components into PDU on UPS.

6

Connect power to UPS.

If you are installing the Symmetra RM UPS:

If the planned power load is less than or equal to 5 kVA, plug the line

into an appropriate outlet.

If the planned power load is greater than 5 kVA, a qualified electrician

must hard wire the input power.

If you are installing the Symmetra UPS:

Regardless of the power load, a qualified electrician must hard wire

the input power.