Ups upgrade, Ups upgrade 195, Adding a ups 195 – HP StorageWorks 8000 NAS User Manual
Page 197
NAS 8000 System and Hardware Upgrades 195
NA
S 80
00
S
ys
tem
a
nd
Har
dwar
e Upg
ra
de
s
UPS Upgrade
Adding a UPS
The following UPS systems can be added to the HP NAS 8000 solution after
the time of purchase. The specific model of UPS recommended is customized
each region:
■
American Power Conversion (APC) Symmetra RM (8U)
■
American Power Conversion (APC) Symmetra RM (15U)
■
American Power Conversion (APC) Symmetra
To install the UPS on the HP NAS 8000 solution, follow these steps:
1
Follow the instructions that came with the UPS for power requirements.
2
Power down all of the solution components in the following sequence
before installing the UPS:
—
NAS server(s)
—
Quorum server (for high-availability configurations)
—
Array
—
FC switch (for high-availability configurations)
—
Library
3
Install the UPS in the bottom of the rack to avoid having a top-heavy rack
and to eliminate the risk of tip over.
4
Connect the communications port on the UPS to the server's COM1 serial
port.
5
Plug components into PDU on UPS.
6
Connect power to UPS.
■
If you are installing the Symmetra RM UPS:
—
If the planned power load is less than or equal to 5 kVA, plug the line
into an appropriate outlet.
—
If the planned power load is greater than 5 kVA, a qualified electrician
must hard wire the input power.
■
If you are installing the Symmetra UPS:
—
Regardless of the power load, a qualified electrician must hard wire
the input power.