Environmental Monitoring Unit

UltraSCSI RAID Enclosure 3–19

Nonoperational Enclosure

Probable Cause 1—Either +5 V dc or 12 V dc out of range. Observe the individual power supply
status LEDs to determine the defective power supply and replace it.

Probable Cause 2—TERMPOWER less than +4.5 V dc on one or more I/O modules. Replace the
I/O modules displaying a TERMPOWER LED O

FF

indication.

Single Blower Fault

Operational blowers are running at
high-speed.

Missing Blower Fault
or
Multiple Blower Faults

Operational blowers are running at
high-speed.

Probable Cause 1—A blower is removed. Replace the missing blower.

Probable Cause 2—All blowers in one bank are not operating. Remove and install blowers correctly
within 8 minutes.

Probable Cause 3—Multiple blowers are installed incorrectly. Remove and install blowers correctly
within 8 minutes.

Comment—In this example, one of the following conditions exist in shelf bank 1:

A blower is removed.

Two or more blowers are not operating.

Failure to replace the missing or defective blowers within 8 minutes might result in the enclosure
entering standby power mode.