Temperature fault led, Power status led, Maintenance terminal connector – HP Array Controller HSG V8.7 Software User Manual
Page 62: Blower fault leds, Power status led –6
Environmental Monitoring Unit
3–6 UltraSCSI RAID Enclosure
Temperature Fault LED
If either the intake or exhaust air temperature exceeds user-defined
temperature setpoints, this amber LED (C
ALLOUT
3) turns O
N
. The
LED remains O
N
until the overtemperature condition is corrected.
Power Status LED
This green power status LED (C
ALLOUT
4) turns O
N
if all the
following normal operating conditions exist:
•
+5 V dc is greater than +4.7 V dc.
•
+12 V dc is greater than +11.4 V dc.
•
At least four power supplies are operational.
•
TERMPOWER is present on all six I/O modules.
The power status LED turns O
FF
if any one of the following error
conditions exist:
•
+5 V dc is less than +4.7 V dc.
•
+12 V dc is less than +11.4 V dc.
•
Fewer than four power supplies are operational.
•
TERMPOWER is missing from one or more I/O modules.
Maintenance Terminal Connector
This connector (C
ALLOUT
5) is used to connect the optional
maintenance terminal or a personal computer (PC) to the EMU for
displaying EMU:
•
Error messages
•
Information messages
This connector and a PC are also used to load microcode updates into
EMU memory.
Blower Fault LEDs
One or more of these eight amber blower fault LEDs (C
ALLOUT
6)
turn O
N
if one of the following error conditions exist:
•
One or more blowers are not operational.
•
One or more blowers are not operating at the correct speed.
•
A blower is removed.