UltraSCSI Enclosure Specifications

UltraSCSI RAID Enclosure A–3

Operating Environments

Table A–1, Table A–2, and Table A–3 provide the environmental
specifications for the controller shelf.

Table A–1 Optimum Operating Environment

Condition

Specification

Temperature

18–24°C (64–75°F) with an average rate of change of 3°C/h maximum and a
step change of 3°C/h or less

Relative humidity

40–60% (noncondensing) with a step change of 10% or less (noncondensing)

Altitude

Up to 2400 m (8000 ft)

Air quality

Not to exceed a maximum of 500,000 particles, 0.5 micron or larger, per cubic
foot of air

Nominal airflow

50 cubic ft/min

Heat dissipation

3070 BTUs/h

Table A–2 Minimum Operating Environment

Condition

Specification

Temperature

10–40°C (50–104°F)
Reduce rating by 1.8°C for each 1000 m altitude (1°F for each 1000 ft of
altitude)

Relative humidity

10–85% at a maximum wet bulb temperature of 32°C (90°F) and a minimum
dew point of 2°C (36°F)

Altitude

Up to 2400 m (8000 ft)

Air quality

Not to exceed a maximum of 500,000 particles, 0.5 micron or larger, per cubic
foot of air

Nominal airflow

40 cubic ft/min

Heat dissipation

3070 BTUs/h