Table 3–2 emu set point temperature conversions, E table 3–2, Table 3–3 – HP Array Controller HSG V8.7 Software User Manual
Page 67
Environmental Monitoring Unit
UltraSCSI RAID Enclosure 3–11
Note
For detailed instructions about using the
set emu
commands, refer to the array controller CLI documentation.
Table 3–2
EMU Set Point Temperature Conversions
°F
°C
°F
°C
°F
°C
°F
°C
°F
°C
32
0
50
10
68
20
86
30
104
40
34
1
52
11
70
21
88
31
106
41
36
2
54
12
72
22
90
32
108
42
37
3
55
13
73
23
91
33
109
43
39
4
57
14
75
24
93
34
111
44
41
5
59
15
77
25
95
35
113
45
43
6
61
16
79
26
97
36
115
46
45
7
63
17
81
27
99
37
117
47
46
8
64
18
82
28
100
38
118
48
48
9
66
19
84
29
102
39
120
49
Table 3–3
Temperature Set Point Rules—EMU Firmware
Versions 1.0 and 1.1
1.
Enter all temperatures in degrees Celsius (°C). Do not use fractions,
decimals, or degrees Fahrenheit (°F).
2.
The EMU set point (sensor_3) temperature must be a minimum of
6°C (11°F) greater than the highest expected ambient (intake)
temperature.
3.
The backplane set points (sensor_1 and sensor_2) must be the same
temperature and a minimum of 13°C (23°F) greater than the highest
expected ambient temperature. This requires a minimum setting of
7°C (13°F) greater than the EMU set point.