background image

Power capping 45

02: Enabled

03: Enabled

04: Enabled

05: Enabled

06: Enabled
This example is with the Power Management Controller (SL Chassis) Firmware version 4.3 only.
> show power 1 3
MDM Port Node Avg Min Max

---- ---- ---- ----- ----- -----

1 3 1 254 n/a 337 (DC watts)

1 3 2 255 n/a 340 (DC watts)

1 3 3 244 n/a 324 (DC watts)

1 3 4 233 n/a 315 (DC watts)

1 3 5 265 n/a 351 (DC watts)

1 3 6 258 n/a 344 (DC watts)

1 3 7 238 n/a 325 (DC watts)

1 3 8 259 n/a 346 (DC watts)

1 3 Fans 20 (DC watts)

1 3 2033 (Chassis total - DC watts)

1 3 2148 (Chassis total - AC watts)

1 3 2247 (Chassis cap - AC

watts)
Total servers = 8

Total chassis = 1

Total fan wattage = 20 (DC watts)

Total system wattage = 2033 (DC watts)

Total system wattage = 2148 (AC watts)
> show power baseline
All values listed are in AC watts

APMPort DMPort Serial Number Min Cap Max Cap Set Cap Slots Populated

------- ------ ------------- ------- ------- ------- ----- ----------------

1 3 0000000000 2242 4744 0 (8) 1 2 3 4 5 6 7 8

1 4 845 4744 0 (8) 1 3

------- ------- -------

3087 9488 0
> show power
MDM Port Node Avg Min Max

---- ---- ---- ----- ----- -----

1 1 (no SL enclosure present)

1 2 (no SL enclosure present)

1 3 1 255 n/a 337 (DC watts)

1 3 2 256 n/a 340 (DC watts)

1 3 3 245 n/a 324 (DC watts)

1 3 4 235 n/a 315 (DC watts)

1 3 5 267 n/a 351 (DC watts)

1 3 6 263 n/a 344 (DC watts)

1 3 7 237 n/a 325 (DC watts)

1 3 8 256 n/a 346 (DC watts)

1 3 Fans 21 (DC watts)

1 3 2042 (Chassis total - DC watts)

1 3 2157 (Chassis total - AC watts)

1 3 2247 (Chassis cap - AC

watts)

1 4 1 92 n/a 188 (DC watts)