SUMMIT 8800

APPENDIX3: MODBUS COMMIUNICATION PROTOCOL

12

12. APPENDIX 3: MODBUS COMMUNICATION PROTOCOL

Modbus commands 01, 02, 03, and 04 are supported for data reads and Modbus commands 05

and 10 are supported for Modbus writes.

The highest accuracy of numbers is achieved using double precision IEEE numbers to 64 bit

resolution. All numbers can be selected as types other than their default.

Variable address types

Any address in the range 0H to FFFFH or 0D to 65535D ID name of variable from data tree

Note. Read /write is only applicable to items with write access (red ID)

Record

Log record number zero (0) being the most recent log record.

12 .1 Number formats

Type

Bits

Range

Description

Unsigned char

8

0..255

Character or boolean

Unsigned short

integer

16

0..65535

16 bit short integer format

Unsigned long integer 32

0.. 4294967295

32 bit long Integer format

Char

8

-128..127

8 bit character

Short integer

16

32768..32767

16 bit short integer

Long integer

32

2147483648

32 bit long integer

Float

32

-3.4E+38..3.4e+38

7 decimals, Single precision IEEE floating

point

Double

64

-1.7E+308..1.7E+308

16 decimals, Double precision IEEE floating

point

Time

64

SSMMHHWDDDmmYYmS

Time format:

Description

Valid range

SS

Seconds

0 to 59

MM

Minutes

0 to 59

HH

Hours

0 to 23 (0=midnight)

WD

Week day

1 to 7 (1=Sunday)

DD

Day

1 to 31

mm

Month

1 to 12

YY

Years

0 to 99 (assumed to be 20xx)

mS

Milliseconds
00

zero

25

250 mS

50

500 mS

75

750 mS

255

Invalid clock (RTC device error)