Modbus commands 01, 02, 03, and 04 are supported for data reads and Modbus commands 05
and 10 are supported for Modbus writes.
The highest accuracy of numbers is achieved using double precision IEEE numbers to 64 bit
resolution. All numbers can be selected as types other than their default.
Variable address types
Any address in the range 0H to FFFFH or 0D to 65535D ID name of variable from data tree
Note. Read /write is only applicable to items with write access (red ID)
Record
Log record number zero (0) being the most recent log record.
12 .1 Number formats
Type
Bits
Range
Description
Unsigned char
8
0..255
Character or boolean
Unsigned short
integer
16
0..65535
16 bit short integer format
Unsigned long integer 32
0.. 4294967295
32 bit long Integer format
Char
8
-128..127
8 bit character
Short integer
16
32768..32767
16 bit short integer
Long integer
32
2147483648
32 bit long integer
Float
32
-3.4E+38..3.4e+38
7 decimals, Single precision IEEE floating
point
Double
64
-1.7E+308..1.7E+308
16 decimals, Double precision IEEE floating
point
Time
64
SSMMHHWDDDmmYYmS
Time format:
Description
Valid range
SS
Seconds
0 to 59
MM
Minutes
0 to 59
HH
Hours
0 to 23 (0=midnight)
WD
Week day
1 to 7 (1=Sunday)
DD
Day
1 to 31
mm
Month
1 to 12
YY
Years
0 to 99 (assumed to be 20xx)
mS
Milliseconds
00
zero
25
250 mS
50
500 mS
75
750 mS
255
Invalid clock (RTC device error)