beautypg.com

8 .4 .1 modbus slave port selection and settings, 8 .4 .1 .1 modbus slave port settings – KROHNE Summit 8800 Vol 3 User Manual

Page 132

background image

132

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol3 R02 en

SUMMIT 8800

COMMUNICATION

08

In the Summit, the modbus slave is completely configurable and can be setup to include any

Summit information in any of the modbus registers. This means that the Summit is capable to

adapt itself to match any of the host devices.

Note: As modbus is not a well defined standard, familiarity with communication and the Mod-

bus protocol is assumed on the part of the user. For further information on modbus please see

website: http://www.simplymodbus.ca or http://en.wikipedia.org/wiki/Modbus

8 .4 .1 Modbus slave port selection and settings

The modbus slave settings are divided in 4 parts: the port settings, the timeout setting, the log

settings and the register settings.

8 .4 .1 .1 Modbus slave port settings

In Hardware select the desired board and port from the left hand list and with modbus slave:

Figure 178 Example RS232/485 Modbus serial and TCP/IP port settings

Settings are needed to match the port with the master device it is intended to be used with.

Please consult master device user manual for further details.

For a serial port set the following parameters:

Modbus ID

The modbus identifier for this link (1..255). When multiple SUMMIT’s are sharing one

RS485 link in a multi-drop configuration, each SUMMIT will need a unique identification.

Setup Name

Any descriptive name to identify communication port

Protocol

ASCII, RTU or RMG. RTU is regarded as the most efficient protocol.

Baud rate

The speed of transmission in bits per second between 300 and 38400.

Parity

A check on correct transmission: none, odd, even, space or mark.

Stop bits

Gap between two transmitted words, 1 or 2 stop bits

Mode

RS232 or RS 485

Word size

Size of one word: 7 or 8 bits