beautypg.com

KROHNE Summit 8800 Vol 3 User Manual

Page 137

background image

137

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol3 R02 en

SUMMIT 8800

COMMUNICATION

08

Latch

Data can be latched (or frozen) until a new latch command is given. Normally all

variables will be updated every calculation cycle. However the variables might be

read slower than they are updated. In this case you can read data from two different

calculation cycles by latching them as one consistent set of data.

To do so, specify “latched” you will then be asked for a register address which is used

to latch the data. By specifying the same address to all data from the consistent set, all

data will be frozen, until a write to the latch address is performed. The contents of the

register can be any variable, e.g., time or none.

Access

Read only or read / write. Access default is read only. Read / write is only applicable to

items with write access capabilities and are indicated by a red ID colour, such as time.

Access control will be important to ensure the security of the SUMMIT 8800. Only give

read/ write access if absolutely required, specifically the Read Write to Data Flash.

Registers

In the different types of Modbus, there are two types of registers: fixed or variable sized

registers, relating to the number of bytes in a register.

In fixed sized registers the number of bytes is independent of the variable in the register.

This means that if the variable is bigger than the register size, multiple addresses must

be used. Often the size is 2 bytes, so to transfer a float (4 bytes) two adjacent addresses

will be used.

In variable sized registers a variable will always use one address. So address 100 may

contain an integer (2 bytes) or a double (8 bytes).

In the flow computer it is possible to define how many registers are used to retrieve

the data. Default is 1 meaning that variable size is assumed. If fixed sized registers are

needed, increase the number. Since the number of addresses for a register may change

an overlap of addresses might occur, the software will warn the user and ask to update

automatically.

For log data such as in Enron or Pemex modbus:

Indexing method

There are 3 indexing methods:
- Direct

The log number is specified in the parameter log number

- Indexed

The log number is specified by the number of records in the modbus request

- Event

The number of records parameter in the modbus request is ignored. The response

is the number of log events which have occurred since the Log was last read and

acknowledged. If no events have occurred then the response is no data. If many

events have occurred, and fill the available modbus response, the oldest events will

be transmitted. More recent events will be transmitted after the last request has

been acknowledged. To obtain the number of events waiting to be transmitted, this is

obtained by accessing the “Modbus Log Event Index”

Log number

In direct indexing method, the record number in the log. Zero is the most recent log

record.

To Acknowledge events, the “Force single Coil” command is issued to the event address.

Note:

Log items and non-log items can only share the same address when the indexing method for

the logged item(s) is set to direct. Where logged items share an address, they must all have the

same indexing method.

Figure 186 Modbus slave im- and export