www.krohne.com

08/2013 - MA SUMMIT 8800 Vol3 R02 en

SUMMIT 8800

COMMUNICATION

08

The settings needed are:

Inter-packet delay In a noisy environment characters may be lost causing two packets frames

to be mixed. This is prevented by putting a delay at the end of each packet. Not needed for TCP/

IP.

Timeout

Time to stop connectivity attempts between the devices

Retries

Number of attempts to establish communication before an alarm is given

Read delay

As the device has to process the read command, it might be needed a delay before the

actual data arrive.

Modbus ID

Unique identifier for the Modbus device

In the stream flow computers, the Modbus slave is defined in a file with the same name as the

master, which can be imported as a modbus list.

8 .3 .6 Gas chromatographs

For gas measurement a gas chromatograph or GC is often needed. Several popular GC’s can be

selected:

Emerson

Daniel 2251
Daniel 2350
Daniel 2551

Yamatake

HGC303

ABB

ABB 8000
ABB 8000S
ABB 8200

Siemens

Maxum II

Instromet

Encal 3000

Contact KROHNE as your GC may already be available or may be created for you. Other GC’s can

be created using the custom Modbus master.

All chromatographs have very similar settings consisting of device and component settings. The

device settings are: