Door holders – Edwards Signaling 2400 Series User Manual
Page 75

0
0
24
24
115
115
230
230
NC
NC
NC
C
C
C
NO
NO
NO
ON
ON
MR-101 (MR-104)
SPDT CONTACTS
10 AMPS @
115 VAC
MR-201 (MR-204)
DPDT CONTACTS
10 AMPS @ 115 VAC
AUX
AUX
AUX
ALARM
ALARM
ALARM
TROUBLE
TROUBLE
TROUBLE
SIG1
SIG1
SIG2
SIG2
INP1
INP1
INP2
INP2
PGM
MODE
PGM
MODE
+
+
+
+
+
+
+
+
+
+
+
CONTROL PANEL
CONTROL PANEL
CONTROL PANEL
CITY TIE/RELAY MODULE
CAT.# 2400-RCT
REFER TO
RELAY/CITY-TIE
DRAWING SHEET
FOR JUMPER
CONFIGURATION
OR
+
+
+
NOTES
NOTES
1. FAILSAFE WIRING SHOWN. ANCILLARY RELAYS ARE NORMALLY
ENERGIZED AND WILL DE-ENERGIZE ON ALARM.
1. CONTACTS SHOWN IN NORMAL
CONDITION.
2. USE OF RELAY/CITY-TIE MODULE PROVIDES ENABLE/DISABLE
CAPABILITY FOR ANCILLARY RELAYS.
3. STANDBY BATTERY CALCULATION REQUIRED. SEE APPENDIX FOR
SPECIFIC INFORMATION.
8. REFER TO APPENDIX FOR COMPATIBLE DEVICES.
9. USE ONLY DOCUMENTED APPLICATIONS.
4
6
7
10
10
4
CONTACT RATING 24 VDC @ 1 AMP.
AUXILIARY POWER 24 VDC @ 500 mA.
POWER LIMITED WIRING.
NON-POWER LIMITED WIRING.
WIRING IS SUPERVISED FOR SHORTS AND GROUND FAULTS.
JUMPERS
1, 2, AND 8
INSTALLED
EDWARDS ULI LISTED
1500 SERIES
DOOR HOLDERS
24 VAC @ .11 AMPS
(9 DEVICES MAX.)
120 VAC
UTILITY
LISTED
FIRE PROTECTIVE
SIGNALING TRANSFORMER
120/24V, 50/60 HZ., 40 VA
DOOR HOLDERS
2. WIRING RUNS ARE NOT
SUPERVISED.
[ELOZRLY2.CDR]
03/08/95
ENABLE/DISABLE
SWITCH
5
5
5
7
6
6
7
+
NC/O
C
TB2
TB1
1
1
2
2
3
3
4
5 6 7 8
JP1
JP2
U10