33 9.0 specifications – Edwards Signaling 2400 Series User Manual
Page 41

33
9.0 SPECIFICATIONS
Table 9.1 - Specifications
Base Panel Assemblies
Dimensions (HWD)
2412 & 2414 Panels
Back box
Finished
2418 Panel
Back box
Finished
12" x 14" x 2.75" [30.5 cm x 35.6 cm x 7.0 cm]
14" x 15.75" x 1.125" [35.6 cm x 40.0 cm x 2.9 cm]
13" x 20.19" x 2.75" [33.0 cm x 51.3 cm x 7.0 cm]
15" x 22" x 1.125" [38.1 cm x 55.9 cm x 2.9 cm]
Weight (less battery)
2412 Panel
2414 Panel
2418 Panel
12 lbs. (5.5 Kg)
12.5 lbs. (5.7 Kg)
16 lbs. (7.3 Kg)
Input Power
120 VAC @ 3.5 A, 50 - 60 Hz
Output Power - Signals
24 VDC @ 4A. Refer to Compatibility Section.
Auxiliary Power
Maximum Capacitance
24 VDC nominal @ 500 mA., filtered, reset
programmable. Refer to Compatibility Section.
100
m
F
Option Module Spaces
2412 Panel: 3 Input/Output
2414 Panel: 2 Input/Output
2418 Panel: 3 Output
Battery Type
2412 & 2414 Panels
2418 Panel
2400-BATBOX(R) Battery Cabinet
2 x 12 V, 6.5 AH, Lead-Acid
2 x 12 V, 6.5 AH, Lead-Acid
4 x 6 V, 8.0 AH, Lead-Acid
2 x 12V, 10 AH Lead-Acid
Ground Fault Detection
10K
Ω
to earth, all field wiring except AC input and
common relay contacts
IDC Zones
Style
Configurations
Two Class B (Style B) or Class A (Style D)
Verified or non-verified alarm
Waterflow or waterflow with retard
Supervisory
Detector Capacity per IDC Circuit
30 - photoelectric smoke
50 - ionization smoke
Detector voltage 17.85 to 26.4 VDC.
Max. Ripple = 400 mVDC
Max. Alarm Current = 33 mADC.
Refer to Compatibility Section.
2-Wire Relay Bases are NOT supported.
Supervisory Series & EOL Resistors
(P/N 46071-0409 for ULI)
(2 each P/N EOL-P1 for ULC)
1.1K
Ω
, 1 Watt; 3.6K
Ω
, 1/2 Watt
IDC End-Of-Line Resistor
4.7K
Ω
, 1/2 Watt
Max. IDC Circuit Field Wiring Resistance
50
Ω
IAC Circuits
Two Class B (Style Y), optional Class A (Style Z)
IAC Output Power/Ckt
Nominal 24 VDC @ 2.5A; 4.0 Amp total for both zones
IAC EOL
4.7K
Ω
, 1/2 Watt
System Alarm Relay
Form C, 24 VDC @1 A. Refer to Compatibility Section for
proper installation.
System Trouble Relay
Form C, 24 VDC @1 A. Refer to Compatibility Section
for proper installation.
Indicators
Power, System Trouble, Zone Disabled, Alarm Silenced,
Alarm, Signal circuit trouble (2), and Ground Fault LEDs
Controls
Trouble Silence, Alarm Silence, Reset, and Zone
Enable/Disable Switches
Max. Battery Charger Current
500 mADC