Edwards Signaling 2400 Series User Manual
Page 47

39
Table 10.3 - 24 Hours Supervisory, 30 Minutes of Alarm
Signal Circuit Current for 30 Minutes
Aux. Circuit Current: 0-0.5 Amps for 30 Minutes
Panel Current Load
Signal Circuit Alarm Current (A)
Aux. Sup
Current
#
Option
Modules
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0 mA
Amp/Hour Battery Size
“
0
4.5
4.5
4.5
4.5
4.5
6.5
6.5
6.5
“
1
4.5
4.5
4.5
4.5
6.5
6.5
6.5
6.5
“
2
4.5
4.5
4.5
6.5
6.5
6.5
6.5
6.5
“
3
4.5
4.5
6.5
6.5
6.5
6.5
8.0
8.0
“
4
4.5
4.5
6.5
6.5
6.5
8.0
8.0
8.0
“
5
6.5
6.5
6.5
6.5
8.0
8.0
8.0
8.0
“
6
6.5
6.5
6.5
6.5
8.0
8.0
8.0
-
25 mA
Amp/Hour Battery Size
“
0
4.5
4.5
4.5
6.5
6.5
6.5
6.5
8.0
“
1
4.5
4.5
4.5
6.5
6.5
6.5
6.5
8.0
“
2
4.5
4.5
6.5
6.5
6.5
6.5
8.0
8.0
“
3
4.5
6.5
6.5
6.5
6.5
8.0
8.0
8.0
“
4
6.5
6.5
6.5
6.5
8.0
8.0
8.0
-
“
5
6.5
6.5
6.5
6.5
8.0
8.0
-
-
“
6
6.5
6.5
6.5
6.5
8.0
-
-
-
50 mA
Amp/Hour Battery Size
“
0
4.5
4.5
6.5
6.5
6.5
6.5
8.0
8.0
“
1
4.5
6.5
6.5
6.5
6.5
8.0
8.0
8.0
“
2
6.5
6.5
6.5
6.5
8.0
8.0
8.0
-
“
3
6.5
6.5
6.5
8.0
8.0
8.0
-
-
“
4
6.5
6.5
6.5
8.0
8.0
8.0
-
-
“
5
6.5
6.5
8.0
8.0
8.0
-
-
-
“
6
6.5
8.0
8.0
8.0
-
-
-
-
75 mA
Amp/Hour Battery Size
“
0
4.5
6.5
6.5
6.5
6.5
8.0
8.0
8.0
“
1
6.5
6.5
6.5
6.5
8.0
8.0
8.0
-
“
2
6.5
6.5
6.5
8.0
8.0
8.0
-
-
“
3
6.5
6.5
8.0
8.0
8.0
-
-
-
“
4
6.5
8.0
8.0
8.0
-
-
-
-
“
5
8.0
8.0
8.0
-
-
-
-
-
“
6
8.0
8.0
8.0
-
-
-
-
-
100 mA
Amp/Hour Battery Size
“
0
6.5
6.5
6.5
8.0
8.0
8.0
-
-
“
1
6.5
6.5
6.5
8.0
8.0
8.0
-
-
“
2
6.5
6.5
8.0
8.0
8.0
-
-
-
“
3
6.5
8.0
8.0
8.0
-
-
-
-
“
4
8.0
8.0
8.0
-
-
-
-
-
“
5
8.0
8.0
-
-
-
-
-
-
“
6
8.0
-
-
-
-
-
-
-