Edwards Signaling 2400 Series User Manual
Page 57

49
ULC Compatibility Listings
Compatible devices listed in this section are for use in CANADA ONLY.
Table 10.9 - ULC Control Unit Compatibility Specifications - Edwards
Electrical Data
Device
ULC Smoke
Detector
Compatibility ID
Standby
Voltage @
Detector
Ripple
Voltage
Maximum Standby Detector Load
EOL
Style B
Style D
2412
2 zone-3 space
panel
0.0
17.85 -26.4 VDC
400 mV
2.5 mA @ 22.3 VDC
N/A
4.7K
Ω
P/N EOL-P1
2414
4 zone-2 space
panel
0.0
17.85 -26.4 VDC
400 mV
2.5 mA @ 22.3 VDC
N/A
4.7K
Ω
P/N EOL-P1
2418
8 zone-3 space
panel
0.0
17.85 -26.4 VDC
400 mV
2.5 mA @ 22.3 VDC
N/A
4.7K
Ω
P/N EOL-P1
2400-2IDC
2 Zone IDC
Module
(P/N 240457)
0.0
17.85 -26.4 VDC
400 mV
2.5 mA @ 22.3 VDC
N/A
4.7K
Ω
P/N EOL-P1
2400-BPA
Base Panel Class
A Converter
(P/N 46199-1072)
0.0
17.85 -26.4 VDC
400 mV
N/A
2.5 mA @
22.3 VDC
N/A
2400-IDCA
IDC Converter
(P/N 46199-1074)
0.0
17.85 -26.4 VDC
400 mV
N/A
2.5 mA @
22.3 VDC
N/A
Table 10.10 - ULC Compatible Receivers for the DL1 Dialer Module
Model
Manufacturer
Location
685
Alarm Device Manufacturing Co.,
Div. of Pittway Corp.
Syosset, NY 11791
CP220
Fire Burglary Instruments,
Div. of Pittway Corp.
Syosset, NY 11791
Quick Alert II
Osborne - Hoffman Inc.
Point Pleasant Beach, NJ 08742
D6500
Radionics Inc.
Salinas, CA 93912
9000
Silent Knight Security Systems,
Div. of Willknight Inc.
Maple Grove, MN 55369