36

Table 9.10- Specifications

DL1 Dialer Module

Expansion Space

1

Phone Line:

Wall Connector

Two Loop Start lines on Public switched telephone
network, Pulse or DTMF dialing.
Standard RJ-31X jack

Line Supervision

Trouble when line voltage < 10 V & line current < 5
mA.

Communications Protocol

SIA pulse format P3, 20 PPS, 4/2, double round,
1400 Hz handshake,
1900 Hz carrier

Telephone Numbers

Two, 24 digit numbers

FCC Registration Number

4Z2USA-22549-AL-E

Dialing Retries

5 to 10

AC Power Failure Delay

0 to 18 hours

Clock Accuracy

Within one hour/year

Compliance

Communications Canada CS-03
FCC / CFR 47 Parts 15 & 68
NFPA 72; UL 864; ULC S527-M87; FM

Programming Phone

Any Tone dial (DTMF) Phone with RJ11 plug

Weight

0.4 lbs (0.18 Kg)

DL1 Dialer Codes

Event Condition

Event Code

Event Condition

Event Code

Zone 1

Alarm

11

Zone 6

Alarm

61

Supervisory Alarm

12

Supervisory Alarm

62

Trouble

13

Trouble

63

Restore

14

Restore

64

Supervisory Restore

15

Supervisory Restore

65

Zone 2

Alarm

21

Zone 7

Alarm

71

Supervisory Alarm

22

Supervisory Alarm

72

Trouble

23

Trouble

73

Restore

24

Restore

74

Supervisory Restore

25

Supervisory Restore

75

Zone 3

Alarm

31

Zone 8

Alarm

81

Supervisory Alarm

32

Supervisory Alarm

82

Trouble

33

Trouble

83

Restore

34

Restore

84

Supervisory Restore

35

Supervisory Restore

85

Zone 4

Alarm

41

Panel

Normal 24 Hr.
Check in

90

Supervisory Alarm

42

Trouble

93

Trouble

43

Restore

94

Restore

44

AC Power Fail

96

Supervisory Restore

45

Abnormal 24 Hr.
Check in

97

Zone 5

Alarm

51

Telephone Line trbl

98

Supervisory Alarm

52

Dialer Disabled

99

Trouble

53

Restore

54

Supervisory Restore

55