Edwards Signaling 2400 Series User Manual
Page 44

36
Table 9.10- Specifications
DL1 Dialer Module
Expansion Space
1
Phone Line:
Wall Connector
Two Loop Start lines on Public switched telephone
network, Pulse or DTMF dialing.
Standard RJ-31X jack
Line Supervision
Trouble when line voltage < 10 V & line current < 5
mA.
Communications Protocol
SIA pulse format P3, 20 PPS, 4/2, double round,
1400 Hz handshake,
1900 Hz carrier
Telephone Numbers
Two, 24 digit numbers
FCC Registration Number
4Z2USA-22549-AL-E
Dialing Retries
5 to 10
AC Power Failure Delay
0 to 18 hours
Clock Accuracy
Within one hour/year
Compliance
Communications Canada CS-03
FCC / CFR 47 Parts 15 & 68
NFPA 72; UL 864; ULC S527-M87; FM
Programming Phone
Any Tone dial (DTMF) Phone with RJ11 plug
Weight
0.4 lbs (0.18 Kg)
DL1 Dialer Codes
Event Condition
Event Code
Event Condition
Event Code
Zone 1
Alarm
11
Zone 6
Alarm
61
Supervisory Alarm
12
Supervisory Alarm
62
Trouble
13
Trouble
63
Restore
14
Restore
64
Supervisory Restore
15
Supervisory Restore
65
Zone 2
Alarm
21
Zone 7
Alarm
71
Supervisory Alarm
22
Supervisory Alarm
72
Trouble
23
Trouble
73
Restore
24
Restore
74
Supervisory Restore
25
Supervisory Restore
75
Zone 3
Alarm
31
Zone 8
Alarm
81
Supervisory Alarm
32
Supervisory Alarm
82
Trouble
33
Trouble
83
Restore
34
Restore
84
Supervisory Restore
35
Supervisory Restore
85
Zone 4
Alarm
41
Panel
Normal 24 Hr.
Check in
90
Supervisory Alarm
42
Trouble
93
Trouble
43
Restore
94
Restore
44
AC Power Fail
96
Supervisory Restore
45
Abnormal 24 Hr.
Check in
97
Zone 5
Alarm
51
Telephone Line trbl
98
Supervisory Alarm
52
Dialer Disabled
99
Trouble
53
Restore
54
Supervisory Restore
55