EMO‐3000

 

Operation and Programming Manual 

 

 

 

44 

      
 

mA Out Offset 

Used to bias the analog output signal to a preset level. Any value from 0.00to 20.00 mA’s is valid. The 
most common is 4.00mA’s.  

 

Use higher offset values in PID mode, particularly if the cracking pressure of the regulator is higher than 
normal.  

USED IN: 

 

PID and Monitor mode 

RELATED VARIABLES: 

 

mA shifter, mA gain 

HEX ADDRESS: 

 

0091 HEX  ‐‐‐‐>  SAME ADDRESS AS IN EMO‐2000 

BYTES: 

 

2 Bytes        DEFAULT: 819 (4.00mA) 

ASC form COMMAND: 

 

reading = 111; writing = 511; E returns the mA’s value; N returns 
counts.  

mA Gain factor  

Used to scale the analog output to the expected input frequency. This scaling factor only applies in 
monitor mode and does not affect PID. Since the top frequencies are anywhere from 3 Hz to 2000Hz, 
there has to be a scaling possibility. Apply this formula to scale the gain factor correctly: 

GAIN = mA’s x 8350/freq 

where 

 mA’s represents the requested mA’ output at the frequency  
 freq is the top frequency expected at 20mA’s 

The default value 167 causes the input frequency of 1000 Hz to generate a 20.00 mA output. 

USED IN: 

 

Monitor mode 

RELATED VARIABLES: 

 

mA shifter, mA gain, mA pointer 

HEX ADDRESS: 

 

0091 HEX  ‐‐‐‐>  SAME ADDRESS AS IN EMO‐2000 

BYTES: 

 

2 Bytes        DEFAULT: 167 

ASC form COMMAND: 

 

reading = 116; writing = 516; E and N return an integer number.  

 