beautypg.com

Emo‐3000 – AW Gear Meters EMO-3000 User Manual

Page 42

background image

EMO‐3000

 

Operation and Programming Manual 

 

 

 

41 

      
 

Integral factor for PID A_KI (I‐part) 

The integral factor is added to the analog output register as long as the set‐value is above the current 
rate. Conversely, the integral part is deducted if the set‐value is below the current rate. This 
adding/subtracting occurs every time new information is available. This variable is used in systems 
where gain factors have to be kept small in order to avoid instability. 

USED IN: 

 

PID mode. 

RELATED VARIABLES: 

 

A_KD/A_KP 

HEX ADDRESS: 

 

00A1 HEX  ‐‐‐‐>  NEW LOCATION FOR THIS VARIABLE 

BYTES: 

 

2 Bytes        DEFAULT: 0 

ASC form COMMAND: 

 

reading = 115; writing = 515; E and N both have the same effect 
value.  

Derivative factor for PID A_KD  (D‐part)  

The derivative factor is used in applications where high gains (A_KP) are needed and instability is to be 
avoided. The derivative factor takes effect if the rate approaches the set‐value, by slowing the approach 
down. Like the gain factor, the derivative factor is usually determined by empiric means. Normal values 
are 0 to 500. 

USED IN: 

 

PID mode. 

RELATED VARIABLES: 

 

A_KI/A_KP 

HEX ADDRESS: 

 

009F HEX  ‐‐‐‐>  NEW VARIABLE 

BYTES: 

 

2 Bytes        DEFAULT: 0 

ASC form COMMAND: 

 

reading = 114; writing = 514; E and N both have the same effect 
value.  

Delta step for PID  

Delta step determines when a new variable is accepted into the scratch pad table. In general, when the 
range the closed loop covers is very wide, the delta step should be relatively large. With the delta step, it 
is possible to manipulate the adaption speed. Program this variable from 0 to 600 Hz. 

USED IN: 

 

PID mode. 

RELATED VARIABLES: 

 

A_KD/A_KP/A_KI