Input‐ouput pin control, Emo‐3000 – AW Gear Meters EMO-3000 User Manual
Page 15

EMO‐3000
Operation and Programming Manual
14
Input‐Ouput Pin Control
You can set pins 11‐14 as inputs or outputs – it depends on the operating mode you select. In monitor
mode, all of the pins are limit outputs. In PID mode, pins 11, 12, and 13 are inputs, while pin 14 is an
output. By setting these Inputs and Outputs to suit the needs of the operating mode, as shown below,
you can take advantage of the LIMIT programming and PID the special functions for more efficient
operations. The standard configuration of these 4 opto‐coupler chips is for the PID mode.
Refer to appendix H for location of the opto‐couplers. Pin 6 on the opto‐coupler IC must be cut off. Refer
to Appendix P for external connections.
PID Mode Configuration
PIN 11
U13
INPUT
TRANSPARENT
PIN 12
U12
INPUT
HOLD ANALOG OUT
PIN 13
U11
INPUT
HOLD TOTALIZER
PIN 14
U10
OUTPUT
SETPOINT REACHED
Monitor Mode Configuration
PIN 11
U13
OUTPUT
LIMIT 1
PIN 12
U12
OUTPUT
LIMIT 2
PIN 13
U11
OUTPUT
LIMIT 3
PIN 14
U10
OUTPUT
LIMIT 4
To modify the standard configuration for the Monitor operating mode, change the three opto‐coupler
chips set for INPUT to OUTPUT. This enables the LIMIT outputs as shown above.
Notice