EMO‐3000

 

Operation and Programming Manual 

 

 

 

42 

      
 

USED IN: 

 

PID mode. 

HEX ADDRESS: 

 

00A7 HEX  ‐‐‐‐>  NEW VARIABLE 

BYTES: 

 

2 Bytes        DEFAULT: 7 cc/m 

ASC form COMMAND: 

 

reading = 117; writing = 517; E and N both have the same effect 
value.  

Delay for PID  

Every time a correction based on a table pick is made to the analog output, any further action is delayed 
by the programmed amount. This feature is needed when long delays in the mechanical system cause 
the closed loop control to “over react.” Program this variable from 00 to 600 seconds. 

USED IN: 

 

PID mode. 

RELATED VARIABLES: 

 

A_KD/A_KP/A_KI 

HEX ADDRESS: 

 

00AB HEX  ‐‐‐‐>  NEW VARIABLE 

BYTES: 

 

2 Bytes        DEFAULT: .80 sec 

ASC form COMMAND: 

 

reading = 108; writing = 508; E and N both have the same effect 
value.  

Kick for PID 

The kick is used in systems where the fluid regulator closes the flow before 4 mA’s output. Often this is a 
sign of a poorly matched system or of a large hysteresis in the regulator. The kick takes effect if: 

 rate is less than cutoff 
 analog output is less than the kick value  (this is measured on top of the offset value) 
 set value is active (greater than 0) 

The kick value is generally a number from 0 to 4095. The number reflects the amount of analog step that 
is added to the mA Offset. Each analog step represents approximately .004 mA’s. Equation is: 

20mA ‐mA Offset 

4095 

The Kick Value is added to the mA Out Offset value. 

USED IN: 

 

PID mode. 