EMO‐3000

 

Operation and Programming Manual 

 

 

 

35 

      
 

USED IN: 

 

All modes. 

RELATED VARIABLES:   

Engineering units for Total. 

HEX ADDRESS: 

 

0018 HEX  ‐‐‐‐‐‐> same address used in EMO‐2000 

BYTES: 

 

4 Bytes                  DEFAULT: xxx 

ASC form: 
COMMAND: 

 

reading = 101; writing = 501; E is engineering units; E is in selected 
engineering units with units attached. N is normalized units in pulses. 

Grand totalizer for A  

This is the grand total of the channel A. The grand total is a product of adding total_A and grand total. 
When the intermediate totalizer is zeroed (keyboard or hardware), the EMO‐3000 adds total_A to the 
grand total. Therefore, we can view the total_A as the “job” total.

 

USED IN: 

 

All modes. 

RELATED VARIABLES: 

 

Engineering units for Total. 

HEX ADDRESS: 

 

0018 HEX and 00F8 HEX, new for the EMO‐3000. 

BYTES: 

 

4 Bytes                  DEFAULT: xxx 

ASC form COMMAND: 

 

reading = 129; writing = 529; E is engineering units; E is in selected 
engineering units with units attached. N is normalized units in Hertz 
down to 1/100

th

Active set value for PID  

The active set value selected is either the value calculated by taking the 0 ‐ 20 milli Amps in with the milli 
Amps scaler or the digital PID set‐value. The milliamps input is the overriding set value. The judgment 
whether mA’s are active is based on the milli Amps in offset. 

 USED IN: 

 

PID mode. 

RELATED VARIABLES: 

 

Digital set value/mA’s in and mA scaler/mA’s in offset 

HEX ADDRESS: 

 

0043 HEX ‐‐‐‐> same address used in EMO‐2000 

BYTES: 

 

4 Bytes                  DEFAULT: xxx 

ASC form 
COMMAND: 

 

reading = 102; writing = 502; E is engineering units; E is in selected 
engineering units with units attached. N is normalized units in Hertz