beautypg.com

0 maintenance and service, 1 troubleshooting, 2 maintenance and service procedures – Condec DLR3110 User Manual

Page 43: 1 panel/chassis removal and installation, Maintenance and service, Panel/chassis removal and installation

background image

Maintenance and Service

39

7.0

Maintenance and Service

The following sections cover troubleshooting, maintenance and service procedures for the DLR3110.

7.1

Troubleshooting

7.2

Maintenance and Service Procedures

This section outlines the mechanical and basic electrical repair procedures for the rack-mount pneumatic
pressure calibrator, model DLR3110. The repair procedures cover the major components and sub-assemblies that
are critical to the proper functioning of the calibrators and that need periodic maintenance over the life of the
unit. Only those persons who are formally trained as skilled technicians should attempt to repair these units. All
relevant safety precautions should be observed due to the presence of electrical components and high-pressure
components.

NOTE: Based on model, the following may give information on components that are not part of your DLR3110.

7.2.1

Panel/Chassis Removal and Installation

Removal

Tools required:

Phillips screwdriver

1. Vent system and remove input pressure source. Disconnect power cord, hoses, connectors, etc. from rear

of DLR3110. Remove from rack, if applicable, by grasping the handles located on the front of the unit
and gently set the rack-mount assembly on a bench top. It can be rested on the panel bottom and chassis
edge.

2. Loosen and remove the three screws (PN 14839) from rear and sides that secure the cover to the chassis.

Installation

Tools required:

Phillips screwdriver

1. Align mounting holes of cover with chassis and install three screws (PN 14839) from rear and sides that

secure the cover to the chassis.

2. Lift the panel and chassis by grasping the handles located on the front of the unit and re-install in rack, if

applicable. Connect input pressure source, power cord, hoses, connectors, to rear of DLR3110.

Symptom

Problem

Remedy

No lit display

Unit does not energize

Check fuse, check power source, check
power switch

Display slowly decreases over time

Leak in system

Check all compression and pipe fittings

with SNOOP

®

*

, bottle of liquid leak gas

detector (PN 64781)

*SNOOP

®

is a registered trademark of Swagelok.

Display does not respond when Vernier

knob is turned

No Vernier control

Readjust isolation valves on Orion;
replace O-ring on Vernier piston

Display increases or decreases when

INPUT (Pressure) or VENT valves are

closed

No Pressure or Vent control

Replace valve seats or o-rings in valves;
check valve needles

Unit will not stay in CAL, display shows
"-0L- -OVER-", or display reads a high

value @ zero PSIG

Transducer over-pressurized

Replace transducer

Display does not zero

Display does not zero

Perform a ZERO/SPAN calibration

Display shifts, is not steady

Transducer drifts or possible over
pressure

Replace transducer

Table 7-1. DLR3110 Troubleshooting