App index, List of attributes – Yokogawa Removable Chassis DX1000N User Manual
Page 43
2-13
IM 04L41B01-04E
Advanced Settings of Screen and Component
1
2
3
App
Index
List of Attributes
Attribute
Description
Default value
ID
Number automatically assigned for component identification.
88 to 91
Batch group no
only with additional
spec. /BT2
Set the batch group number. The batch number needs to
be between [1] and number of Multi batch configured at the
basic settings.
The batch group number will be displayed only when Multi
batch is valid.
1
Group no
Set the group number.
Multi batch Off
You can select a number from [1] to [10] for DX1000, and [1]
to [36] for DX2000.
Multi batch On
You can select a number from [1] to [6] for DX1000, and [1]
to [12] for DX2000.
1
Kind
Set the scale kind.
[Off]: The value is not displayed.
[On]: Scale values will be displayed by the number of
partitions configured, at previously defined intervals.
[Bitmap]: Use a bitmap image for the scale. If files specified
under [Bmp filename] cannot be loaded, the scale
the scale is displayed with the kind set to Off.
On
Trend direction
Set the direction of a wave. You can select [SET], [Horizon],
or [Vertical].
SET
Form
Set the size of SCALE. You can select either [Small] or
[Large].
Small
Bmp filename
Enter the name of a bitmap file saved on an external
storage medium (CF card).
The read destination is the directory used when the screen
was loaded.
Bitmap.bmp
Indicator
Set how the current value is displayed.
You can select [SET], [Mark], or [Bar].
Note that this field will not be available when the type is set
to [Off].
SET
Indicator type
Set the indicator format to [Normal], [Micro], [Small], or
[Balanced].
See “Parts of the component and indicator types” on page
2-12.
Normal
Digit
Set the number of digits for the value displayed at the scale.
You can select [SET], [Normal], or [Fine].
You can set this field only when the Kind is set to [On].
SET
Margin
Sets whether or not to display a margin on both sides in the
direction of the span.
[On]: Display a margin of 3% of component width (or height)
in the direction of the scale
[Off]: Margin not displayed
Off
Change group
Sets whether or not to switch the group display in the
execution panel when the left/right keys are pressed.
[On]: Display switched [Off]: Display not switched
On
Alarm mark
display
Set how the alarm set-point mark is displayed.
You can select [On], [Off], or [SET].
SET
Alarm mark
Set the type of alarm set-point mark.
You can select [Alarm], [Fixed], or [SET].
SET
Unit
Selects whether or not to display the units.
[On]: Units displayed [Off]: Units not displayed
On
2nd span
You can choose to validate or invalidate the 2nd span by
setting [On] or [Off].
See Section 2.2.
Off
2nd span Lower
Enter a value between 0.0% for the lower limit and 100.0%
for the upper limit. In this case, the difference between the
two spans needs to be 10.0% or greater.
See Section 2.2
0.0
Continued on next page
2.6 Attributes of Scale Components