Group Control Settings
Group control is set up in the attribute dialog boxes of each individual component.
Tag (ID:0) attribute setting dialog box
Uses
GR. CRTL 1.
Because this component is associated
with the first registered channel of each display group, set
1.
The settings can be displayed in the GR. CTRL. dialog box. They can also be edited.
These are the IDs of the components associated with the channel registered
first in each display group.
These are the IDs of the components associated with the channel registered
second in each display group.
Order means the order of channel registrations in the display group settings.
In this example, channels 001, 003, 005, and 007 are registered to order 1.
This is the group number displayed when moving to the execution screen.
When switching the display group in the execution screen, this number also
changes to the displayed group number.
By repeatedly pressing the right arrow key, the screen changes in the order: display
group 1 -> display group 2 -> display group 3 -> display group 4 -> display group 1… and
so on. Pressing the left arrow key changes the screens in reverse order. Display groups
turned Off in the group settings do not appear among the switched screens.