beautypg.com

Specifications, A.18 – Watlow Series 97 User Manual

Page 80

background image

A . 1 8

A p p e n d i x

Wa t l o w S e r i e s 9 7

Electromechanical Relay

• Form C contact configuration
• Minimum load current 10mA @ 5V

Î

(dc)

• Rated resistive and inductive loads: 2A @ 250V

Å

(ac) or

30V

Î

(dc) maximum

• Electrical life 100,000 cycles at rated current
• For resistive loads only, must use RC suppression for

inductive loads

Retransmit

• Range selectable: 0-20mA, 4-20mA, 0-5V

Î

(dc),

1-5V

Î

(dc), 0-10V

Î

(dc)

• 0 to 10V

Î

(dc) voltage output into a 1,000

minimum load

resistance

• 0 to 20mA current output into an 800

maximum load

resistance

• Resolution:

dc ranges = 2.5mV nominal
mA ranges = 5µA nominal

• Calibration accuracy:

dc ranges = ±15mV
mA ranges = ±30µA

• Temperature stability 100ppm/°C

Communications

• EIA/TIA-485, EIA/TIA-232
• Opto-isolated
• Modbus

RTU protocol

• 1200, 2400, 4800, 9600, 19200 baud rates
• 32 maximum units can be connected (With additional 485

repeater hardware, up to 247 units may be connected)

Accuracy

• Input ranges

Type J:

32 to 1382°F or

0 to 750°C

Type K:

-328 to 2282°F or -200 to1250°C

Type T:

-328 to

662°F or -200 to 350°C

Type N:

32 to 2282°F or

0 to1250°C

Type E:

-328 to 1470°F or -200 to 900°C

Type C(W5):

32 to 4200°F or

0 to2315°C

Type D(W3): 32 to 4200°F or

0 to2315°C

Type PTII:

32 to 2540°F or

0 to1393°C

Type R:

32 to 2642°F or

0 to1450°C

Type S:

32 to 2642°F or

0 to1450°C

Type B:

1598 to 3092°F

or 870 to1700°C

DIN: -328

to 1472°F or -200 to 800°C

JIS: -328

to 1166°F

or -200 to 630°C

Thermocouple Inputs

• Calibration accuracy ±0.1% of span ±1°C at standard

conditions
Exceptions:
Type T; 0.12% of span for -200°C to -50°C,
Types R and S; 0.15% of span for 0°C to 100°C
Types B; 0.24% of span for 870°C to 1700°C

• Accuracy span: 540°C/1000°F minimum
• Temperature stability: ±0.1 degree per degree change in

ambient

Specifications

(2195)

Controller

• Microprocessor-based, user selectable control modes
• Input sample period; Single input 10Hz (100 msec), dual input

5Hz (200 msec) digital filter adjustable

• Display update; 2Hz (500 msec), time filter adjustable
• Input/Output/Communication isolation
• Displayed in °C or °F

Operator Interface

• Dual 4-digit LED displays: upper 10.2 mm (0.4 in), lower 6.2

mm (0.244 in)

• Advance, Up Arrow, Down Arrow, Reset tactile keys

Standard Conditions For Specifications

• Ambient temperature 25°C/77°F ±3°C, rated line voltage, 50 to

60Hz, 0 to 90% RH non-condensing,
15 minute warm-up

Universal Input 1
Thermocouple

• Type J, K, T, N, C (W5), E, PTII, D (W3), B, R, S thermocouple

types

• >20M

input impedance

• Maximum 20

source resistance

• 30mA open detection bias

RTD

• 2- or 3-wire platinum, 100

• DIN and JIS curves
• Whole or tenth degree indication
• 150µA nominal RTD excitation currrent

Input 2
Event Input

• Contact or voltage
• 20K

input impedance

• Voltage input: event high state 3 to 36V

Î

(dc),

event low state 0 to 2V

Î

(dc)

• Resistance/contact input: event high state > 23k

, event low

state 0 to 2k

Output Types
Open Collector/Switched DC

• Open collector configuration:

Maximum voltage 42V

Î

(dc)

Maximum current 200mA
Maximum “on” resistance 1.1

Maximum offstate leakage current 100µA

• Switched dc configuration:

Switched dc supply voltage 22 to 28V

Î

(dc)

dc supply current limited to 30mA

Solid-state Relay

• Optically isolated
• Zero cross switched
• Without contact suppression
• Minimum load current 0.5mA rms
• Maximum current 0.5A rms at 20 to 280V

Å

(ac)

• Maximum offstate leakage current 10µA rms
• For resistive loads only, must use RC suppression for

inductive loads