Wa t l o w S e r i e s 9 7

W i r i n g

3 . 1 1

NOTE:

Successful installation
requires five steps:
• Choose the controller’s

hardware configuration
and model number
(Appendix);

• Choose a sensor

(Chapters 3 and 6, and
Appendix);

• Install the controller

(Chapter 2);

• Wire the controller

(Chapter 3) and

• Configure the controller

(Chapters 4, 5 and 6).

NOTE:

The CMC converter
requires an external
power supply when used
with a laptop computer.

ç

WARNING:

To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Series 97.
Failure to do so could
result in such damage,
and/or injury or death.

NOTE:

If the system does not
work properly, it may need
termination resistors at
each end of the network. A
typical installation would
require a 120-ohm resistor
across the transmit/receive
terminals (19 and 21) of
the last controller in the
network and the converter
box or serial card. Pull-up
and pull-down resistors
may be needed to main-
tain the correct voltage
during the idle state.

Figure 3.11a — EIA-232 to EIA-485 Conversion

B&B Converter (B&B Electronics Manufacturing Company, (815) 433-5100).

CMC Converter (CMC Connecticut Micro-Computer, Inc., 800-426-2872).

Figure 3.11b — Termination for EIA-232 to EIA-485 Converter

+5V

B

A

GND

T+/R+

T-/R-

Com

1K

120

1K

Converter box
termination
with pull-up
and pull-down
resistors.

9V

Î

(dc) (see note)

120V

Å

(ac)

COM.

T-/R-

T+/R+

0219-0217-0000

7 ft. comms cable

EIA-232

ADA485L

EIA-485

A

B

A

B

G

9V

Î

G

DI/O

DI/O

21

19

20

T-/R-

TD (A)
TD (B)

RD (A)
RD (B)

T+/R+

120V

~

(ac)

EIA-232

EIA-485

EIA-485

Power S

up

ply

AD-1210

+

GND

GND

COM.

19

20

21

485OIC

+12VÎ(dc)

+12VÎ(dc)

(232 power)