Thermocouple input procedure, Rtd input procedure – Watlow Series 97 User Manual

Page 74

background image

A . 1 2

A p p e n d i x

Wa t l o w S e r i e s 9 7

Thermocouple Input Procedure

Equipment

• Type J reference compensator with reference junction at 32°F/0°C, or type J

thermocouple calibrator to 32°F/0°C.

• Precision millivolt source, 0 to 50mV minimum range, 0.002mV resolution.

Input 1 Setup and Calibration

1. Connect the correct power supply to terminals 8 and 9 (see Chapter Three

and the Appendix).

2. Connect the millivolt source to terminals 6 (-) and 7 (+) with copper wire.

3. Enter 50.000mV from the millivolt source. Allow at least 10 seconds to

stabilize. Set Thermocouple Calibration, 50mV [tc50] (Input Calibration
Menu) to [`yES]. Press the Advance Key ‰ to store 50.000mV input and
move to the next prompt.

4. Enter 0.000mV from the millivolt source. Allow at least 10 seconds to

stabilize. Set Thermocouple Calibration, 0mV [tc00] (Input Calibration
Menu) to [`yES]. Press the Advance Key ‰ to store 0.000mV input and
move to the next prompt.

5. Disconnect the millivolt source and connect the reference compensator or

thermocouple calibrator to terminals 6 (-) and 7 (+). With type J
thermocouple wire, if using a compensator, turn it on and short the input
wires. When using a type J calibrator, set it to simulate 32°F/0°C. Allow 10
seconds for the controller to stabilize. Set Thermocouple Calibration, 32°
[tc32] (Input Calibration Menu) to [`yES]. Press the Advance Key ‰ to
store type J thermocouple calibration and move to the next prompt.

6. Rewire for operation and verify calibration.

RTD Input Procedure

Equipment Required

• 1k

decade box with 0.01

resolution.

Input 1 Setup and Calibration

1. Connect the correct power supply to terminals 8 and 9 (see Chapter Three

and the Appendix).

2. Short terminals 5, 6 and 7 together with less than 0.1

. Set Ground [`gnd]

(Input Calibration Menu) to [`yES]. Press the Advance Key ‰ to store
ground input and move to the next prompt.

2. Short terminals 5 and 7 together with less than 0.5

. Set Lead Resistance

Calibration [LEAd] (Input Calibration Menu) to [`yES]. Press the Advance
Key ‰ to store the lead resistance and move to the next prompt.

4. Connect the decade box to terminals 5 (S2), 6 (S3) and 7 (S1), with 20- to 24-

gauge wire.

5. Enter 15.00

from the decade box. Allow at least 10 seconds to stabilize. Set

RTD Calibration, 15

[r`15] (Input Calibration Menu) to [`yES]. Press

the Advance Key ‰ to store the 15.00

input and move to the next prompt.

6. Enter 380.00

from the decade box. Allow at least 10 seconds to stabilize.