beautypg.com

Output 3 menu, Setup page / output 3 menu – Watlow Series 97 User Manual

Page 51

background image

Active if Output 3 hardware is

present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].

741 r/w

[Al`O]

[Al`O] alarm condition

de-energizes output
(fail safe operation)
(0)

[Al`C] alarm condition

energizes output (1)

[Lgc3] Alarm Logic 3

Selects alarm 3
output condition in
the alarm state.

Active if Output 3 hardware is

present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].

740 r/w

[both]

[both] both (0)
[``hi] high (1)
[``lo] low (2)

[Sid3] Alarm Active

Sides 3

Selects alarm 3 side
option.

Active if Output 3 hardware is

present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].

739 r/w

[``no]

[``no] no action (0)
[`yes] silence 3

enabled (1)

[SiL3] Silencing 3

Enables Silence 3.

Active if Output 3 hardware is

present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].

738 r/w

[``no]

[``no] no action (0)
[`Yes] latching

enabled (1)

[Lat3] Latching 3

Enables Alarm 3
Latching.

Active if Output 3 hardware is

present (97 _ _-_ _ D _-_ _ _ __ ,
Output 3 (Output 3 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].

737 r/w

3

1 to 9999

[hys3] Alarm Hysteresis 3

Sets the switching
hysteresis for the
alarm output. This
defines a band on
the inside of the
alarm set point.
When the process
temperature is in
this band, the alarm
state will not
change.

Active if Output 3 hardware is

present (97 _ _-_ _ D _-_ _ _ _),
Output 3 (Output 3 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].

734 r/w

[`OFF]

[`OFF] off (0)
[`AL`] alarm (1)

[Ot`3] Output 3

Selects type of
output 3.

[Out3]

Output 3 Menu

[`set] Setup Page

Display

Parameter

Range

Default

Modbus

Conditions for

Address

Parameters to Appear

read/write

Wa t l o w S e r i e s 9 7

P a r a m e t e r s

6 . 1 1

Setup Page / Output 3 Menu

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.