Modbus register numbers, Modbus™ register numbers . . . . . . .a.8, Modbus registration numbers . . . . . . . .a.8 – Watlow Power Series Rev H User Manual
Page 62
A . 8
■
Wa t l o w P o w e r S e r i e s
A p p e n d i x
1
Unit Serial Number High Digits
2
Unit Serial Number Low Digits
4
Software Version
5
Manufactured Date (yymm)
7
Hardware Version
30
Software Build Number
50
Unit Current Rating (Amps)
51
Unit Voltage Rating (Volts)
52
Number Zones Configured
53
Hardware Configured Type
54
Configuration Installed Options
55
Power Control Algorithm Select
56
Fixed Time Base (Sec)
57
Factory Safety Shutdown Temp
58
Load Type Select (Control Zone 1 only,
3 Phase only.)
80
Voltage Compensation (On/Off)
85
Comms Watchdog Select (On/Off)
86
Comms Watchdog Timeout (S)
87
Comms Watchdog Failure Output Power
Select
150
Analog (mA) Input 1 Signal
151
Analog (V) Input 1 Signal
152
Line Potential (Volts) rms Line 1
153
A/D Counts Input 1
154
Load Current (Amps) rms Line 1
155
Single Phase 0.1 kVA Zone 1
156
Load Power (kVA) Zone 1
157
Heater Bakeout Timeout Zone 1
159
Output 1 Power (%)
160
Analog (mA) Input 2 Signal
161
Analog (V) Input 2 Signal
162
Line Potential (Volts) rms Line 2
163
A/D Counts Input 2
164
Load Current (Amps) rms Line 2
165
0.1 kVA Zone 2
166
Load Power (kVA) Zone 2
167
Heater Bakeout Timeout Zone 2
169
Output 2 Power (%)
170
Analog (mA) Input 3 Signal
171
Analog (V) Input 3 Signal
172
Line Potential (Volts) rms Line 3
173
A/D Counts Input 3
174
Load Current (Amps) rms Line 3
175
0.1 kVA Zone 3
176
Load Power (kVA) Zone 3
177
Heater Bakeout Timeout Zone 3
179
Output 3 Power (%)
180
Active Alarms
181
Heater Open alarm
182
Heater Tolerance Alarm
183
Heat Sink Over Temperature Alarm
184
Line Loss Alarm
185
Phase Balance Alarm
186
Load Balance Alarm
187
Frequency Out of Tolerance Alarm
188
Line Compensation Alarm
189
Line Over Voltage Alarm
190
Communications Watchdog Alarm
195
Active Errors
198
Line Frequency (Hz)
850
Active Relay State
851
Global Alarm Configuration
860
Heater Open Alarm Config.
861
Heater Tolerance Alarm Config.
862
Over Temperature Alarm Config.
863
Line Loss Alarm Configuration
864
Phase Balance Alarm Config.
865
Load Balance Alarm Config.
866
Frequency Out of Tolerance Alarm
Configuration
867
Voltage Compensation Alarm Config.
868
Over Voltage Alarm Config.
869
Comms Watchdog Alarm Configuration
870
Retransmit Config. Select
871
Retransmit Type Select
872
Retransmit Phase Select
873
Retransmit Zone Select
876
Minimum Amps Retransmit
877
Maximum Amps Retransmit
878
Minimum kVA Retransmit
879
Maximum kVA Retransmit
880
Set Retransmit Output Low Voltage (Volts)
881
Set Retransmit Output High Voltage (Volts)
882
Set Retransmit Output Low Current (mA)
883
Set Retransmit Output High Current (mA)
950
Restore Data Set
951
Backup Data Set
952
Default Data Set
959
Enable NVOL Storage
990
Heat Sink Alarm Temp
991
Load Balance Percentage
1350
Global Lockout
1351
Control Setup Menus Lockout
1352
Options Setup Menus Lockout
1353
Alarms Setup Menu Lockout
1354
Comms Setup Menu Lockout
1355
Retransmit Setup Menu Lockout
1356
Analog Input Factory Menus Lockout
1357
Retransmit Cal Factory Menu Lockout
1358
System Data Factory Menu Lockout
1359
Diagnostics Factory Menu Lockout
1513
Display Test
1540
Line Loss Alarm, Most Recent Type, Line 1
1541
Line Loss Alarm, Previous Type, Line 1
1542
Line Loss Alarm, Least Recent Type, Line 1
1543
Line Loss Alarm, Most Recent Type, Line 2
1544
Line Loss Alarm, Previous Type, Line 2
1545
Line Loss Alarm, Least Recent Type, Line 2
1546
Line Loss Alarm, Most Recent Type, Line 3
1547
Line Loss Alarm, Previous Type, Line 3
1548
Line Loss Alarm, Least Recent Type, Line 3
1555
Retransmit Set Test Word
1560 to 1573 Read Selected A/D Counts
1580
Select Discrete Input
1581
Read Selected Input Value
1590
Heat Sink Temp (°C)
1591
Record High Heat Sink Temp
1700
Factory Mode Request
1799
Factory Password Entry
1960
Accum Hours (10K - 100M)
1961
Accum Hours (0 - 9999)
5011
Set Analog Input Low Current Scale (mA)
Zone 1
5012
Set Analog Input High Current Scale (mA)
Zone 1
5013
Set Analog Input Low Voltage Scale (Volts)
Zone 1
5014
Set Analog Input High Voltage Scale (Volts)
Zone 1
5019
Learn Input Request (Hi, Lo) Zone 1
5021
Set Analog Input Low Current Scale (mA)
Zone 2
5022
Set Analog Input High Current Scale (mA)
Zone 2
5023
Set Analog Input Low Voltage Scale (Volts)
Zone 2
5024
Set Analog Input High Voltage Scale (Volts)
Zone 2
5029
Learn Input Request (Hi, Lo) Zone 2
5031
Set Analog Input Low Current Scale (mA)
Zone 3
5032
Set Analog Input High Current Scale (mA)
Zone 3
5033
Set Analog Input Low Voltage Scale (Volts)
Zone 3
5034
Set Analog Input High Voltage Scale (Volts)
Zone 3
5039
Learn Input Request (Hi, Lo) Zone 3
5101
Input Signal Method Select (dig, mA, Volt)
Zone 1
5102
Numeric (%) Input 1 Signal
Modbus Register Numbers
Relative Parameter Numbers (For Absolute Numbers, add 40001 to the Relative Number.)
5103
Default Numeric Input Signal (%)
Zone 1
5104
Maximum Rate of Change (%/100msec)
Zone 1
5105
Soft Start Time (Sec) Zone 1
5106
Inductive Load Factor Request Zone 1
5107
Inductive Load Current Zone 1
5110
Heater Bakeout Select (On/Off) Zone 1
5111
Heater Bakeout Select Time Zone 1
5112
Current Limit Select (On/Off) Zone 1
5113
Current Limit Set Point (A) Zone 1
5114
Low Tolerance Set Point (A) Zone 1
5115
High Tolerance Set Point (A) Zone 1
5116
Heater Bakeout Overcurrent Trip Zone 1
5201
Input Signal Method Select (dig, mA,
Volt) Zone 2
5202
Numeric (%) Input 2 Signal
5203
Default Numeric Input Signal (%)
Zone 2
5204
Maximum Rate of Change (%/100msec)
Zone 2
5205
Soft Start Time (Sec) Zone 2
5206
Inductive Load Factor Request Zone 2
5207
Inductive Load Current Zone 2
5210
Heater Bakeout Select (On/Off) Zone 2
5211
Heater Bakeout Select Time Zone 2
5212
Current Limit Select (On/Off) Zone 2
5213
Current Limit Set Point (A) Zone 2
5214
Low Tolerance Set Point (A) Zone 2
5215
High Tolerance Set Point (A) Zone 2
5216
Heater Bakeout Overcurrent Trip Zone 2
5301
Input Signal Method Select (dig, mA,
Volt) Zone 3
5302
Numeric (%) Input 3 Signal
5303
Default Numeric Input Signal (%)
Zone 3
5304
Maximum Rate of Change (%/100msec)
Zone 3
5305
Soft Start Time (Sec) Zone 3
5306
Inductive Load Factor Request Zone 3
5307
Inductive Load Current Zone 3
5310
Heater Bakeout Select (On/Off) Zone 3
5311
Heater Bakeout Select Time Zone 3
5312
Current Limit Select (On/Off) Zone 3
5313
Current Limit Set Point (A) Zone 3
5314
Low Tolerance Set Point (A) Zone 3
5315
High Tolerance Set Point (A) Zone 3
5316
Heater Bakeout Overcurrent Trip Zone 3
5411
Adjust Low mA Cal Point Zone 1
5412
Adjust High mA Cal Point Zone 1
5413
Adjust Low V Cal Point Zone 1
5414
Adjust High V Cal Point Zone 1
5415
Calibrate Analog Input Request Zone 1
5421
Adjust Low mA Cal Point Zone 2
5422
Adjust High mA Cal Point Zone 2
5423
Adjust Low V Cal Point Zone 2
5424
Adjust High V Cal Point Zone 2
5425
Calibrate Analog Input Request Zone 2
5431
Adjust Low mA Cal Point Zone 3
5432
Adjust High mA Cal Point Zone 3
5433
Adjust Low V Cal Point Zone 3
5434
Adjust High V Cal Point Zone 3
5435
Calibrate Analog Input Request Zone 3
5591
Baseline Voltage Learn Request Zone 1
5592
Baseline Voltage Learn Request Zone 2
5593
Baseline Voltage Learn Request Zone 3
5594
Baseline Voltage Read/Adjust Zone 1
5595
Baseline Voltage Read/Adjust Zone 2
5596
Baseline Voltage Read/Adjust Zone 3
5700
Cal Retransmit Request
5710
Retransmit Cal mA Low
5711
Retransmit Cal mA High
5720
Retransmit Cal Volts Low
5721
Retransmit Cal Volts High