Modbus register numbers, Modbus™ register numbers . . . . . . .a.8, Modbus registration numbers . . . . . . . .a.8 – Watlow Power Series Rev H User Manual

Page 62

background image

A . 8

Wa t l o w P o w e r S e r i e s

A p p e n d i x

1

Unit Serial Number High Digits

2

Unit Serial Number Low Digits

4

Software Version

5

Manufactured Date (yymm)

7

Hardware Version

30

Software Build Number

50

Unit Current Rating (Amps)

51

Unit Voltage Rating (Volts)

52

Number Zones Configured

53

Hardware Configured Type

54

Configuration Installed Options

55

Power Control Algorithm Select

56

Fixed Time Base (Sec)

57

Factory Safety Shutdown Temp

58

Load Type Select (Control Zone 1 only,
3 Phase only.)

80

Voltage Compensation (On/Off)

85

Comms Watchdog Select (On/Off)

86

Comms Watchdog Timeout (S)

87

Comms Watchdog Failure Output Power
Select

150

Analog (mA) Input 1 Signal

151

Analog (V) Input 1 Signal

152

Line Potential (Volts) rms Line 1

153

A/D Counts Input 1

154

Load Current (Amps) rms Line 1

155

Single Phase 0.1 kVA Zone 1

156

Load Power (kVA) Zone 1

157

Heater Bakeout Timeout Zone 1

159

Output 1 Power (%)

160

Analog (mA) Input 2 Signal

161

Analog (V) Input 2 Signal

162

Line Potential (Volts) rms Line 2

163

A/D Counts Input 2

164

Load Current (Amps) rms Line 2

165

0.1 kVA Zone 2

166

Load Power (kVA) Zone 2

167

Heater Bakeout Timeout Zone 2

169

Output 2 Power (%)

170

Analog (mA) Input 3 Signal

171

Analog (V) Input 3 Signal

172

Line Potential (Volts) rms Line 3

173

A/D Counts Input 3

174

Load Current (Amps) rms Line 3

175

0.1 kVA Zone 3

176

Load Power (kVA) Zone 3

177

Heater Bakeout Timeout Zone 3

179

Output 3 Power (%)

180

Active Alarms

181

Heater Open alarm

182

Heater Tolerance Alarm

183

Heat Sink Over Temperature Alarm

184

Line Loss Alarm

185

Phase Balance Alarm

186

Load Balance Alarm

187

Frequency Out of Tolerance Alarm

188

Line Compensation Alarm

189

Line Over Voltage Alarm

190

Communications Watchdog Alarm

195

Active Errors

198

Line Frequency (Hz)

850

Active Relay State

851

Global Alarm Configuration

860

Heater Open Alarm Config.

861

Heater Tolerance Alarm Config.

862

Over Temperature Alarm Config.

863

Line Loss Alarm Configuration

864

Phase Balance Alarm Config.

865

Load Balance Alarm Config.

866

Frequency Out of Tolerance Alarm
Configuration

867

Voltage Compensation Alarm Config.

868

Over Voltage Alarm Config.

869

Comms Watchdog Alarm Configuration

870

Retransmit Config. Select

871

Retransmit Type Select

872

Retransmit Phase Select

873

Retransmit Zone Select

876

Minimum Amps Retransmit

877

Maximum Amps Retransmit

878

Minimum kVA Retransmit

879

Maximum kVA Retransmit

880

Set Retransmit Output Low Voltage (Volts)

881

Set Retransmit Output High Voltage (Volts)

882

Set Retransmit Output Low Current (mA)

883

Set Retransmit Output High Current (mA)

950

Restore Data Set

951

Backup Data Set

952

Default Data Set

959

Enable NVOL Storage

990

Heat Sink Alarm Temp

991

Load Balance Percentage

1350

Global Lockout

1351

Control Setup Menus Lockout

1352

Options Setup Menus Lockout

1353

Alarms Setup Menu Lockout

1354

Comms Setup Menu Lockout

1355

Retransmit Setup Menu Lockout

1356

Analog Input Factory Menus Lockout

1357

Retransmit Cal Factory Menu Lockout

1358

System Data Factory Menu Lockout

1359

Diagnostics Factory Menu Lockout

1513

Display Test

1540

Line Loss Alarm, Most Recent Type, Line 1

1541

Line Loss Alarm, Previous Type, Line 1

1542

Line Loss Alarm, Least Recent Type, Line 1

1543

Line Loss Alarm, Most Recent Type, Line 2

1544

Line Loss Alarm, Previous Type, Line 2

1545

Line Loss Alarm, Least Recent Type, Line 2

1546

Line Loss Alarm, Most Recent Type, Line 3

1547

Line Loss Alarm, Previous Type, Line 3

1548

Line Loss Alarm, Least Recent Type, Line 3

1555

Retransmit Set Test Word

1560 to 1573 Read Selected A/D Counts
1580

Select Discrete Input

1581

Read Selected Input Value

1590

Heat Sink Temp (°C)

1591

Record High Heat Sink Temp

1700

Factory Mode Request

1799

Factory Password Entry

1960

Accum Hours (10K - 100M)

1961

Accum Hours (0 - 9999)

5011

Set Analog Input Low Current Scale (mA)
Zone 1

5012

Set Analog Input High Current Scale (mA)
Zone 1

5013

Set Analog Input Low Voltage Scale (Volts)
Zone 1

5014

Set Analog Input High Voltage Scale (Volts)
Zone 1

5019

Learn Input Request (Hi, Lo) Zone 1

5021

Set Analog Input Low Current Scale (mA)
Zone 2

5022

Set Analog Input High Current Scale (mA)
Zone 2

5023

Set Analog Input Low Voltage Scale (Volts)
Zone 2

5024

Set Analog Input High Voltage Scale (Volts)
Zone 2

5029

Learn Input Request (Hi, Lo) Zone 2

5031

Set Analog Input Low Current Scale (mA)
Zone 3

5032

Set Analog Input High Current Scale (mA)
Zone 3

5033

Set Analog Input Low Voltage Scale (Volts)
Zone 3

5034

Set Analog Input High Voltage Scale (Volts)
Zone 3

5039

Learn Input Request (Hi, Lo) Zone 3

5101

Input Signal Method Select (dig, mA, Volt)
Zone 1

5102

Numeric (%) Input 1 Signal

Modbus Register Numbers

Relative Parameter Numbers (For Absolute Numbers, add 40001 to the Relative Number.)

5103

Default Numeric Input Signal (%)
Zone 1

5104

Maximum Rate of Change (%/100msec)
Zone 1

5105

Soft Start Time (Sec) Zone 1

5106

Inductive Load Factor Request Zone 1

5107

Inductive Load Current Zone 1

5110

Heater Bakeout Select (On/Off) Zone 1

5111

Heater Bakeout Select Time Zone 1

5112

Current Limit Select (On/Off) Zone 1

5113

Current Limit Set Point (A) Zone 1

5114

Low Tolerance Set Point (A) Zone 1

5115

High Tolerance Set Point (A) Zone 1

5116

Heater Bakeout Overcurrent Trip Zone 1

5201

Input Signal Method Select (dig, mA,
Volt) Zone 2

5202

Numeric (%) Input 2 Signal

5203

Default Numeric Input Signal (%)
Zone 2

5204

Maximum Rate of Change (%/100msec)
Zone 2

5205

Soft Start Time (Sec) Zone 2

5206

Inductive Load Factor Request Zone 2

5207

Inductive Load Current Zone 2

5210

Heater Bakeout Select (On/Off) Zone 2

5211

Heater Bakeout Select Time Zone 2

5212

Current Limit Select (On/Off) Zone 2

5213

Current Limit Set Point (A) Zone 2

5214

Low Tolerance Set Point (A) Zone 2

5215

High Tolerance Set Point (A) Zone 2

5216

Heater Bakeout Overcurrent Trip Zone 2

5301

Input Signal Method Select (dig, mA,
Volt) Zone 3

5302

Numeric (%) Input 3 Signal

5303

Default Numeric Input Signal (%)
Zone 3

5304

Maximum Rate of Change (%/100msec)
Zone 3

5305

Soft Start Time (Sec) Zone 3

5306

Inductive Load Factor Request Zone 3

5307

Inductive Load Current Zone 3

5310

Heater Bakeout Select (On/Off) Zone 3

5311

Heater Bakeout Select Time Zone 3

5312

Current Limit Select (On/Off) Zone 3

5313

Current Limit Set Point (A) Zone 3

5314

Low Tolerance Set Point (A) Zone 3

5315

High Tolerance Set Point (A) Zone 3

5316

Heater Bakeout Overcurrent Trip Zone 3

5411

Adjust Low mA Cal Point Zone 1

5412

Adjust High mA Cal Point Zone 1

5413

Adjust Low V Cal Point Zone 1

5414

Adjust High V Cal Point Zone 1

5415

Calibrate Analog Input Request Zone 1

5421

Adjust Low mA Cal Point Zone 2

5422

Adjust High mA Cal Point Zone 2

5423

Adjust Low V Cal Point Zone 2

5424

Adjust High V Cal Point Zone 2

5425

Calibrate Analog Input Request Zone 2

5431

Adjust Low mA Cal Point Zone 3

5432

Adjust High mA Cal Point Zone 3

5433

Adjust Low V Cal Point Zone 3

5434

Adjust High V Cal Point Zone 3

5435

Calibrate Analog Input Request Zone 3

5591

Baseline Voltage Learn Request Zone 1

5592

Baseline Voltage Learn Request Zone 2

5593

Baseline Voltage Learn Request Zone 3

5594

Baseline Voltage Read/Adjust Zone 1

5595

Baseline Voltage Read/Adjust Zone 2

5596

Baseline Voltage Read/Adjust Zone 3

5700

Cal Retransmit Request

5710

Retransmit Cal mA Low

5711

Retransmit Cal mA High

5720

Retransmit Cal Volts Low

5721

Retransmit Cal Volts High