Input wiring, Control power and alarm wiring, Retransmit wiring – Watlow Power Series Rev H User Manual

Page 14: Communications wiring, Figure 3.2a, Figure 3.2b, Figure 3.2c

background image

3 . 2

Wa t l o w P o w e r S e r i e s

W i r i n g , C h a p t e r 3

ç∫

WARNING:

To avoid damage to
property and equipment,
and/or injury or loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Power
Series. Failure to do so
could result in damage,
and/or injury or death.

NOTE:

Input, retransmit and
communications external
terminals have been
designed for protection in
case of direct contact in
accordance with Europ-
pean Standard EN50178.

NOTE:

Insure ground is wired
with the same size wire
as line and load
connections to a ground
of sufficient current
carrying capacity. (Refer
to Chapter 2, p. 2.1,
Power Series Wire
Bending Radius at Base
Current and Ambient
Temperature Rating.)

NOTE:

Torque and wire strip
guidelines:

• Control wiring 1 thru

23.

• Strip wire to 0.24 inch

(6mm). Torque to 8 in.-
lbs. ( 0.9 Nm).

• Hold torque for 30

seconds to allow for
wiring settling and cold
flow. Re-torque after
48 hours.

• All line connections

should be re-torqued
every 3-6 months.

Input Wiring

Figure 3.2a –

Control Power and Alarm Wiring

Figure 3.2b –

Retransmit Wiring

Figure 3.2c –

Communications Wiring

Power Series

6

5

4

3

2

1

11

10

9

8

7

14

13

12

17

16

15

20

19

18

23

22

21

External Connector

COMMS

7 8

485 T/R +

(Common)

9 10 11

232 TRAN (EIA/TIA-232 Transmit Out)

232 REC (EIA/TIA-232 Receive In)

485 T/R -

RETRANSMIT

DC 10V/20mA

Power Series

6

5

4

3

2

1

11

10

9

8

7

14

13

12

17

16

15

20

19

18

23

22

21

External Connector

12 13 14

I

V

+

+

(Current Out, 4 to 20mA)

(Common)

(Voltage Out, 0 to 10V)

Power Series

External Connector

Relay Internal to Power Series

NC

C

NO

L1

L2

L1

L2

208 or 240V~

(Alarm Common)

(Alarm
Normally Open)

(Alarm
Normally Closed)

Unused

120V~

6

5

4

3

2

1

11

10

9

8

7

14

13

12

17

16

15

20

19

18

23

22

21

CONTROLLER

POWER SUPPLY

85 to 265V~ 55VA

L1

Neutral

ALARM

250V~ 3A

1 2 3

4 5 6