beautypg.com

Watlow Power Series Rev H User Manual

Page 34

background image

Active if heater diagnostics option

is installed and heater bakeout
is running in the zone.

157 r [1]
167 r [2]

n/a

[9999] to [```0]

[minutes]
(9999 to 0)

[Hbt1], [Hbt2] Heater

Bakeout Timeout

Displays the time
left on a heater
bakeout.

Active with multizone

configuration.

159 r [1]
169 r [2]

[``)0]

[``)0] to [10)0]

(0 to 1000)

[Out1], [Out2]

Output Power (%)

Displays present out-
put power.

Active with multizone

configuration.

mA, r [1][2]
150,160
V, r [1][2]
151,161
dig, r/w [1][2]
5102, 5202

[``)0]

[``)0] to [1)00] [V]

(0 to 1000)

[``)0] to [2)00] [mA]

(0 to 2000)

[``)0] to [10)0] [%]

(0 to 1000)
0.1 increments

[In`1], [In`2]

Analog (mA or V)
or Numeric (%)
Input Signal
Displays mA/V
analog input; selects
numeric % power.

Active with multizone

configuration.

n/a

1

[```1]

to

[```2]

[```1]

,

[```2]

[2one] Display Zone

Selection

Select Zone 1 or 2 for
display.

Two Zone, Single Phase

Active if heater diagnostics option

is installed.

156 r

n/a

[```0] to [9999]

(0 to 9999)

[`HUa] Load Power

(kVA)

Displays (est.) calcu-
lated load power.

Active if heater diagnostics option

is installed.

164 r

n/a

[```0] to [9999]

(0 to 9999)

[`Cur] Load Current

(Amps) rms

Displays measured
load current.Peak
current converted to
rms, then multiplied
by % power = aver-
age rms current
measured by the on-
board CT.

Active: Always.
Appears in Display Loop.

162 r

n/a

[```0] to [9999]

(0 to 9999)

[`UoL] Line Potential

(Volts) rms
Displays measured
line voltage.

Active if heater diagnostics option

is installed and heater bakeout
is running in the zone.

157 r [1]

n/a

[9999] to [```0]

[minutes]
(9999 to 0)

[`Hbt] Heater Bakeout

Timeout

Displays the time
left on a heater
bakeout.

Active: Always.
Appears in Display Loop.

159 r

[``)0]

[``)0] to [10)0]

(0 to 1000)

[`Out] Output Power (%)

Displays present out-
put power.

6 . 2

Wa t l o w P o w e r S e r i e s

P a r a m e t e r s , C h a p t e r 6

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Address

Parameters to Appear

read/write