*NOTE: These prompts (Backup, Default, and Restore Data Set) allow the user to manipulate the EEPROM contents.
See Appendix, p. A.7, for more information.
Active: Always.
950 r/w
[idle] dis-
able restore
(0)
[idle] (0)
[`all] (1)
[`sys] (2)
[2n`1] (3)
[2n`2] (4)
[2n`3] (5)
NOTE: See “Backup Data
Set” above for description
of the Modbus values 0 - 5.
[rest] Restore Data Set*
Restores the appro-
priate user config-
urable parameters
from backup memo-
ry. See page A.7 for
Power Series Backup
information.
Active: Always.
952 r/w
[idle] dis-
able restore
(0)
[idle] (0)
[`all] (1)
[`sys] (2)
[2n`1] (3)
[2n`2] (4)
[2n`3] (5)
NOTE: See “Backup Data
Set” above for description
of the Modbus values 0 - 5.
[dFLt] Default Data Set*
Sets the appropriate
parameters to the
factory default val-
ues. See page A.7 for
Power Series Backup
information.
Active: Always.
951 r/w
[idle] no
backup re-
quested (0)
[idle] no backup re-
quested (0)
[`all] all parameters
listed in system, zone
1, 2 and 3 (1)
[`sys] system related
parameters, includes
locks, alarms, retrans-
mit, comms, algo-
rithm, load type, volt-
age compensation (2)
[2n`1] zone 1 related
parameters, includes
all parameters in
menus
[Ctr1] and
[Opt1] (3)
[2n`2] zone 2 related
parameters, includes
all parameters in
menus
[Ctr2] and
[Opt2] (4)
[2n`3] zone 3 related
parameters, includes
all parameters in
menus
[Ctr3] and
[Opt3] (5)
[BAuP] Backup Data Set*
Stores appropriate
user configurable
parameters into
backup memory. See
page A.7 for Power
Series Backup infor-
mation.
[dAtA]
System Data Manipulation Menu
[Fcty] Factory Page
This menu is used to maintain the standard and backup system data.
P a r a m e t e r s , C h a p t e r 6
Wa t l o w P o w e r S e r i e s
■
6 . 1 5
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Address
Parameters to Appear
read/write