beautypg.com

Watlow Power Series Rev H User Manual

Page 44

background image

Active if retransmit and heater

diagnostics options are installed.

871 r/w

[`CUr] cur-

rent (1)

[`Off] none (0)
[`CUr] current (1)
[`HUA] kVA (2)

[type] Retransmit Type

Select

Select type of
retransmit informa-
tion; amps or kVA.

Active if retransmit and heater

diagnostics options are installed.

870 r/w

{`nna] mA

(0)

{`nna] mA (0)
{UOlt] volts (1)

[`Cf9] Retransmit

Config. Select

Select type of
retransmit output.

[rEtr]

Setup Retransmit Configuration Menu

[`Set] Setup Page

This menu is used to set up the retransmit parameters. The menu is not available unless

Retransmit and Heater Diagnostics are installed.

Active if serial communications

option is installed and

[`Wd]

Watchdog is set to

{``On].

87 r/w

[``)0] 0 per-

cent (0)

[``)0] 0 percent to

[10)0] 100 percent
(0 to 1000)

[PWr] Watchdog Failure

Output Power
Select

Selects the default
power level for a
watchdog timeout.

Active if serial communications

option is installed and

[`Wd]

Watchdog is set to

{``On].

86 r/w

[9999]

(9999)

[```0] to [9999] (0

to 9999)

[`seC] Watchdog Timeout

(Sec)

Selects a timeout in
seconds for the
communications
watchdog.

Active if serial communications

option is installed.

85 r/w

{`Off] off (0)

{`Off] off (0)
{``On] on (1)

[`Wd] Watchdog Select

(On/Off)

Turns on a watchdog
for communications.

Active if serial communications

option is installed.

[9600] 9600

baud

[1200] 1200 baud
[2400] 2400 baud
[4800] 4800 baud
[9600] 9600 baud
[1(2`] 19.2K baud

[baud] Unit Baud Rate

Select

Select baud rate for
communications.

Active if serial communications

option is installed.

[```1]

[```1] to [`247]

[Addr] Unit Address Select

Select device
address for
communications.

[COm]

Setup Comms Configuration Menu

[`Set] Setup Page

This menu is used to set up the communications parameters. This menu is not available unless

Serial Communications is installed.

6 . 1 2

Wa t l o w P o w e r S e r i e s

P a r a m e t e r s , C h a p t e r 6

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write