beautypg.com

Multizone output wiring, Figure 3.5d, Figure 3.5e – Watlow Power Series Rev H User Manual

Page 17: Fan wiring for 250a models

background image

L2

L1

L3

4

5

6

Limit Control

Contacts

(If Required)

Heater

2

Gnd

1

3

4

5

6

On-board

Semiconductor Fuses

Figure 3.5a – 3-Phase, 3-Leg,

6-SCR Output Wiring for
4-Wire Wye Application
(Model PC4X-XXXX-XXXX)

Figure 3.5b – 3-Phase, 3-Leg,

6-SCR Inside Delta

Figure 3.5c – 3 Phase, 3-Leg,

6-SCR Output Wiring
(Model PC3X-XXXX-XXXX)

L2

L1

L3

Limit Control

Contacts

(If Required)

Gnd

On-board

Semiconductor

Fuses

ref.1

ref. 2

ref. 3

PC9

2

1

3

4

5

6

N

Limit Control

Contacts

(If Required)

L2

L1

L3

2

Gnd

1

3

4

5

6

On-board

Semiconductor

Fuses

ref.1

ref. 2

ref. 3

W i r i n g , C h a p t e r 3

Wa t l o w P o w e r S e r i e s

I

3 . 5

ç∫

WARNING:

To avoid damage to
property and equipment,
and/or injury or loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Power
Series. Failure to do so
could result in damage,
and/or injury or death.

ç

WARNING:

Install high or low
temperature limit control
protection in systems
where an over
temperature fault
condition could present a
fire hazard or other
hazard. Failure to install
temperature limit control
protection where a
potential hazard exists
could result in damage to
equipment, property and
injury to personnel.

NOTE:

For reference
connections 1 to 3, use
QC 0.250 in. wide and
0.032 in. thick
compatible connection
which is fully insulated
with nylon and has a
metal grip ring.

For 14-16 AWG:
Molex/ETC AA-5261; 3M
MNG14-250DFIX C-54-
503X or equivalent.

**NOTE: Models PC8 and PC9 control legs are isolated so that they may be wired from phase-to-phase inside delta or
phase-to-neutral, independent of how the other legs are wired.

çCAUTION: Do not connect ref.
connections with PC3 models. Failure
to follow this guideline could cause
damage to the Power Series.

Note:
Wiring must
be A, B, C
rotation.

Note:

Wiring must be A,

B, C rotation if phase
control is selected.

Limit Control

Contacts

(if required)

L1

L2

Gnd

1

3

4

6

PC8

On-board

Semi-

conductor

Fuses

2 Independent,

Single-phase Heaters

heater 2

ref.1

ref. 3

heater 1

Limit Control

Contacts

(if required)

L2

L1

L3

Gnd

1

3

4

6

PC8

On-board

Semi-

conductor

Fuses

2 Independent,

Single-phase Heaters

heater 2

ref.1

ref. 3

heater 1

Figure 3.5d –

**

Multizone Output Wiring

Figure 3.5e –

Fan Wiring for 250A Models

Note: 1. Phasing must be as shown.

2. Do not connect Ref. terminals.

Gnd

On-board

Semi-

conductor

Fuses

2

1

3

PC9

4

5

6

ref.1

ref. 2

ref. 3

heater

1

heater

3

heater

2

3 Independent,

Single-phase Heaters

Limit Control

Contacts

(if required)

L1

L2

Limit Control

Contacts

(if required)

L2

L1

L3

Gnd

On-board

Semi-

conductor

Fuses

2

1

3

PC9

4

5

6

ref.1

ref. 2

ref. 3

heater

1

heater

3

heater

2

3 Independent,

Single-phase Heaters

PC8X-XXXX-XXX1

PC8X-XXXX-XXX3

PC9X-XXXX-XXX1

PC9X-XXXX-XXX3

Molex/ETC AA-5261; 3M
MNG14-250DFIX
C-54-503X or equivalent.

Note:

Wiring must be A,

B, C rotation if phase