beautypg.com

Serial bus system, Analog input modules, Analog output modules – Ross Controls ROSS MODULAR I User Manual

Page 43

background image

43

www.rosscontrols.com

Analog Input Modules

RPSSNACM12A

RPSSNAVM12A

Number of Inputs

2

2

Keyswitch Position

3

3

Input Signal Range

4…20 mA
0…20 mA

0…10V
±10V

Input Resolution, Bits

16 bits - over 21 mA
0.32 µA/cnt

15 bits plus sign
320 µV/cnt inunipolar or bipolar mode

Absolute Accuracy, Current Input

0.1% Full Scale @ 25°C*

Absolute Accuracy, Voltage Input

0.1% Full Scale @ 25°C*

Input Step Response, per Channel

70 ms @ Notch = 60 Hz (default)
80 ms @ Notch = 50 Hz
16 ms @ Notch = 250 Hz
8 ms @ Notch = 500 Hz

70 ms @ Notch = 60 Hz (default)
80 ms @ Notch = 50 Hz
16 ms @ Notch = 250 Hz
8 ms @ Notch = 500 Hz

Input Conversion Type

Delta Sigma

Delta Sigma

PointBus Current (mA)

75

75

Power Dissipation, Max.

0.6 W @ 28.8VDC

0.6 W @ 28.8VDC

* Includes offet, gain, non-linearity and repeatability error terms.

Analog input modules support these configurable parameters and diagnostics: open-wire with LED and electronic reporting; four-alarm and annunciation

set-points; calibration mode and electronic reporting; under- and over-range and electronic reporting; channel signal range and update rate and on-board scaling;
filter-type; channel update rate.

Analog Output Modules

RPSSTACM12A

RPSSTAVM12A

Number of Outputs

2

2

Keyswitch Position

4

4

Output Signal Range

4…20 mA
0…20 mA

0…10V
±10V

Output Resolution, Bits

13 bits - over 21 mA
2.5 µA/cnt

14 bits (13 plus sign)
1.28 mV/cnt inunipolar or bipolar mode

Absolute Accuracy, Current Output

0.1% Full Scale @ 25°C*

Absolute Accuracy, Voltage Output

0.1% Full Scale @ 25°C*

Step Response to 63% of FS,

24 µs


Current Output

Step Response to 63% of FS,

20 µs
Voltage Output

Output Conversion Rate

16 µs

20 µs

PointBus Current (mA)

75

75

Power Dissipation, Max.

1.0 W @ 28.8VDC

1.0 W @ 28.8VDC

* Includes offet, gain, non-linearity and repeatability error terms.

Analog output modules support these configurable parameters and diagnostics: open-wire with LED and electronic reporting (RPSSTACM12A only); fault mode; idle

mode; alarms; channel signal range and on-board scaling.

Serial Bus System