4.2.4 CONTROL OPTIONS - REMOTE SETPOINT
The 53MC5000 is capable of accepting a setpoint from a remote instrument for loop #1 through
AI2.
1. Configure the RSP input signal parameters:
•
Set C258 to the span (in Engineering Units) and C278 to the minimum (in
Engineering Units) of the RSP range.
•
The 53MC5000 is set to accept a 1-5 V RSP signal. If 0-5 V is required, set
L487=1. The 53MC5000 is set to accept a linear PV signal. If square root extraction
is required, set L442=1.
2. Enable the Remote Setpoint capability by setting L115=1. The 53MC5000 will permit remote set-
point operation if DI0 is closed.
The 53MC5000 is capable of accepting a setpoint from a remote instrument for Loop #2 through
AI3.
1. Configure the RSP input signal parameters:
•
Set C259 to the span (in Engineering Units) and C279 to the minimum (in
Engineering Units) of the RSP range.
•
The 53MC5000 is set to accept a 1-5 V RSP signal. If 0-5 V is required, set
L497=1. The 53MC5000 is set to accept a linear PV signal. If square root extraction
is required, set L443=1.
2. Enable the Remote Setpoint capability by setting L139=1. The 53MC5000 will permit remote set-
point operation if DI1 is closed.